Access Door (20 gauge)/Frame Assembly (16 gauge) (Cold-Rolled, Galvanneal, or Stainless Steel) (Insulated) (Latch-Operated) for installation in Horizontal Floor/Ceiling Assemblies or Vertical Wall Assemblies as noted below.
Maximum Size of Openings: |
Vertical Installation: 48" wide x 48" high
Horizontal Installation: 24" wide x 36" high |
Ratings: |
1 Hour: Wood Framed Assemblies (Horizontal Installation)
3 Hour: Non-Combustible Assemblies (Horizontal Installation)
1-1/2 Hour: (Vertical Installation) |
Testing Standards: UBC 43-7 (Horizontal), UL10B (Vertical), ASTME152 (Vertical).
Insulated vertical installation applications meet 450F temperature rise at 30 minutes.
Licensed Manufacturer
Samson Metal Products, Inc.
City of Commerce, CA 90040
Evaluated to the following:
All assemblies in this section are identified by a label or marking bearing the wording "Listed (Product)", a time interval, a serial number and the Warnock Hersey Certification Mark and are installed in accordance with the following:
NFPA-80, Fire Doors & Windows, or
National Building Code of Canada, and
Manufacturer's Instructions.