Elevator Door/Frame Assemblies
Single or Paired Elevator Entrance Door/Frame Assembly (10, 14, 16 gauge Steel) for installation in 1-1/2 hour locations in drywall or masonry openings.
Limitations: Single Doors/Two Speed Pairs/Center Parting Pairs/Listed Gasketing/Listed Operating Hardware/Dust Covers.
Maximum Size of Frame Openings: |
Singles: 3'6" wide x 7'0" high Pairs: 4'0" wide x 7'0" high |
Maximum Size of Doors: |
Singles - 3'7-1/2" wide x 7'-1/2" high x 1-1/4" thick (minimum) Pairs - 2'3/4" wide x 7'-1/2" high x 1-1/4" thick (minimum) |
|
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Method of Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors & Windows
Manufacturer's Instructions.
All assemblies are identified by a label bearing the wording, "Listed (Product)", a time interval, a serial number and the WHI Certification Mark.