Intertek Directory of Building Products

3M Fire Barrierâ„¢ 1000 NS Silicone Joint Sealant Company: 3M Company

This product is a silicone caulking material used as a fill, void or cavity material in through-penetration firestops.
 
This material is offered in four packaged configurations: 
 
·         10.1 fluid ounce cartridge
·         20 fluid ounce sausage
·         4.5-gallon pail
·         28.0 fluid ounce cartridge
 
RATINGS
 
Standard Rating Design
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-05
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-06
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-07
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-08
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-09
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-10
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-11
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-12
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-13
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-14
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/JS 120-15
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 25% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/JS 120-16
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 25% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 3/4 hr. 3MU/JS 120-17
F Rating – 2 hr.
ASTM E1399/ASTM E2307 / CAN/ULC-S115 Cycling – Class IV
±10% horizontal movement @ 33% compression
±6.25% vertical shear movement @33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 3/4 hr. 3MU/JS 120-18
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
±10% horizontal movement @ 33% compression
±6.25% vertical shear movement @ 33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-19
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1/4 hr. @ 50% Compression 3MU/JS 120-20
T Rating – 0 hr. @ 33% Compression
T Rating – 0 hr. @ 20% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 20% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2 hr. @ 50% Compression 3MU/JS 120-21
T Rating – 1 hr. @ 33% Compression
T Rating – 1/2 hr. @ 25% Compression
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling - Class IV
±16.7% horizontal movement @ 50% compression
±11% horizontal movement @ 33% compression
±5% horizontal movement @ 25% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 1 hr. 3MU/JS 120-22
F Rating – 2 hr.
ASTM E 1399/ASTM E 2307 Cycling –  Static
±0% horizontal movement @ 20% compression
±0% vertical shear movement @ 20% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/JS 120-23
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±10% horizontal movement @ 33% compression
±6.25% vertical shear movement @ 33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-01
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-02
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-03
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-04
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 / CAN/ULC-S115 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-05
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-06
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/JS 180-07
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T-Rating - 1-1/2 hr.  3MU/JS 180-08
F-Rating - 3 hr.
ASTM E1399/ASTM E2307 Cycling - Static
±0% horizontal movement @ 25% compression
±0% vertical shear movement @ 25% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T-Rating - Refer to Design Listing 3MU/JS 180-09
F-Rating - 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
Horizontal movement – Refer to Design Listing
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/JS 180-12
F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
±5% horizontal movement @ 33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/JS 180-13
F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±5% horizontal movement @ 33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/BPF 120-01
F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
±10% horizontal movement @ 33% compression
±6.25% vertical shear movement @ 33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/BPF 180-01
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 Cycling – Class IV
  ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating – 2-1/2hr. @ 50% Compression 3MU/BPF 180-02
  T Rating – 1-1/2 hr. @ 33% Compression
  F Rating – 3 hr.
ASTM E1399/ASTM E2307 ±16.7% horizontal movement @ 50% compression
  ±11% horizontal movement @ 33% compression
  ±6.25% vertical shear movement @ 33% compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2307 T Rating - 1 hr. 3MU/BPF 180-03
F Rating - 3 hr.
ASTM E1399/ASTM E2307 Cycling - Class IV
±16.7% horizontal movement @ 50% compression
±6.25% vertical shear movement @ 50% compression
UL 2079 L Rating <1 SCFM/LF
ASTM E2307 T Rating – 0 hr. 3MU/PFB 120-30
  F Rating – 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 1
ISO 6944 (1985) Duct A only 1 hour (Stability, Insulation, and Integrity) 3MU/DI 60-01
ASTM E814 T Rating - 1 hr.
F Rating - 1 hr.
ISO 6944 (1985) Duct A only 2 hour (Stability, Insulation, and Integrity) 3MU/DI 120-01
ASTM E814 T Rating - 2 hr.
F Rating - 2 hr.
ASTM E2307 T Rating - 0 hr. 3MU/PFB 120-30
F Rating - 1 hr. 
ASTM E1399/ASTM E2307 Cycling – Class 1
±16.7% horizontal movement @ 50% joint packing material compression
 ±6.25% vertical shear movement @ 50% joint packing material compression
 ±5% horizontal movement @ 20% joint packing material compression
ASTM E814 T Rating - 1 hr. 3MU/PV 60-01    (OPL FS 558F)
F Rating - 1 hr.
ASTM E814 T Rating - 2 hr. 3MU/PV 120-03 (OPL FS 560F)
F Rating - 2 hr.
ASTM E814 T Rating - 2 hr. 3MU/PV 120-04  (OPL FS 561F)
F Rating - 2 hr. 
ASTM E814 T Rating - 79 min. 3MU/PV 120-06 (OPL FS 576F)
F Rating - 2 hr.
ASTM E814 T Rating - 2 hr. 3MU/PV 120-07 (OPL FS 578F)
F Rating - 2 hr.
ASTM E814 T Rating - 0 hr. OPL CEJ 371P
F Rating - 2 hr. 
UL 2079 L Rating < 1 SCFM/LF 3MU/JS 120-23 (OPL CEJ 372P)
ASTM E2307 T Rating - 0 hr.
F Rating - 2 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4
±10% horizontal movement @ 33% joint packing material compression
±6.25% vertical shear movement @ 33% joint packing material compression
UL 2079 L Rating < 1 SCFM/LF 3MU/PV 60-03
ISO 6944 (1985) Duct A only 1 hour (Stability, Insulation, and Integrity)
ASTM E814 T Rating - 1 hr.
F Rating - 1 hr.
ASTM E1399/ASTM E2307 Cycling – Class 4 3MU/JS 180-12
±5% horizontal movement @ 33% joint packing material compression
UL 2079  L Rating < 1 SCFM/LF
ASTM E2307 T Rating - 0 hr. 3MU/JS 180-13
F Rating - 3 hr. 
ASTM E1399/ASTM E2307 Cycling – Class 4
±5% horizontal movement @ 33% joint packing material compression
UL 2079 L Rating < 1 SCFM/LF
ASTM E2336 Reference Design listing 3MU/FRD 120-18
3MU/FRD 120-19
ICC-ES AC 101 Noncombustibility Test (ASTM E 136) – Pass
Fire Resistance Test (ASTM E 119) – 2 hr
Durability Test (ASTM C 518 modified) – Pass
Internal Fire Test – 4 hr @ 500°F and 30 minutes @ 2000°F – Pass
Fire-Engulfment Test (ASTM E 119 Exposure) – 2 hr
3MU/FRD 120-18
3MU/FRD 120-19
ISO 6944 (1985) Duct A only 2 hour (Stability, Insulation, and Integrity) 3MU/PV 120-05  (OPL FS 573F)
 
*Note: T-Rating is zero for installation through a fire-rated shaft wall with insulated duct on outside of fire-rated shaft assembly and un-insulated duct on the inside of the shaft assembly, and when the fire exposure is from the side with the insulated duct.

Certified Products can be identified by the Omega Point Laboratories (OPL), Warnock Hersey (WH), or ETL Certification Mark
Listing Report Return to Search
Attributes
CriteriaUL 2079 Air Leakage (2004)
CriteriaASTM E1399 Cycling
CriteriaISO 6944 (1985)
CriteriaASTM E814
CriteriaISO 6944-1 (2008)
CriteriaICC-ES AC101 (2001)
CriteriaASTM E2307 (2010)
CriteriaASTM E814 (2011a)
CriteriaASTM E2336 (2016)
CriteriaUL 2079 Air Leakage (2015)
CriteriaCAN / ULC S115 (2018) Ed. 5
CSI Code07 80 00 Fire and Smoke Protection
CSI Code07 84 43 Fire-Resistant Joint Sealants
CSI Code07 84 13 Penetration Firestopping
CSI Code07 84 53 Building Perimeter Firestopping
Listing SectionFIRESTOP SYSTEMS
Spec ID28789
Design Documents
Public Documents
No Results