The 3M™ Fire Barrier™ CP 25WB+ Caulk product is a one-part, intumescent (expands when heated), elastomeric latex caulk. It is used to seal construction openings, blank openings and penetrating items such as cables and pipe, against the passage of flame, smoke and water. It is also used in conjunction with 3M™ Brand FS-195+ Wrap/Strip and CS-195+ Composite Sheet. The CP 25WB+ Caulk is packaged in 10.1-ounce cartridges, 20-ounce sausage packs, 27-ounce cartridges, 2-gallon pails and 5-gallon pails. The caulk may also be packed into 55-gallon drums for packaging into cartridges and sausage packs.
RATINGS
Standard |
Rating Type |
Rating |
ASTM E 84 |
Flame Spread Index |
Less than or equal to 5 |
Smoke Developed Index |
0 |
Standard |
Rating |
Design Number |
ASTM E 1725 |
2 hour |
3MU/BI 120-02 |
ASTM E 1725 |
1 hour |
3MU/AF 60-01
(ECP 523) |
ASTM E 1725 |
1 hour |
3MU/AF 60-02
(ECP 524) |
ASTM E 1725 |
1 hour |
3MU/AF 60-03
(ECP 525) |
ASTM E 1725 |
1 hour |
3MU/AF 60-4
(ECP 526) |
ASTM E 1725 |
1 hour |
3MU/AF 60-05
(ECP 527) |
ASTM E 1725 |
3 hour |
3MU/AF 180-01
(ECP 528) |
ASTM E 1725 |
3 hour |
3MU/AF 180-02
(ECP 529) |
ASTM E 1725 |
3 hour |
3MU/AF 180-03
(ECP 530) |
ASTM E 1529 |
4 hour |
3MU/AF 240-01
(B 301) |
ASTM E 119 |
4 hour |
3MU/AF 240-02
(B 302) |
Standard |
Size |
Ampacity Derating |
Design Number |
IEEE 848-1996 |
24-inch x 4-inch tray |
49.9% |
3MU/AF 60-06 (ECP 531) |
IEEE 848-1996 |
1-inch conduit |
8% |
3MU/AF 60-07 (ECP 532) |
IEEE 848-1996 |
4-inch conduit |
9% |
3MU/AF 60-07 (ECP 532) |
Standard 1 |
Standard 2 |
Rating |
Design No. |
Integrity |
Stability |
Insulation |
T-Rating |
F-Rating |
ISO 6944 (1985) Duct A |
ASTM E 814 |
2 hr.* |
2 hr.* |
2 hr.* |
2 hr.* |
2 hr.* |
FS 565 W |
ISO 6944 (1985) Duct A |
ASTM E 814 |
2 hr. |
2 hr. |
2 hr. |
2 hr. |
2 hr. |
FS 567 W |
ISO 6944 (1985) Duct A |
ASTM E 814 |
2 hr.* |
2 hr.* |
2 hr.* |
2 hr.* |
2 hr.* |
FS 569 W |
ISO 6944 (1985) Duct A |
ASTM E 814 |
2 hr. |
2 hr. |
2 hr. |
2 hr. |
2 hr. |
FS 571 W |
ISO 6944 (1985) Duct A |
ASTM E 814 |
2 hr. |
2 hr. |
2 hr. |
2 hr. |
2 hr. |
FS 574 W |
ISO 6944 (1985) Duct A |
ASTM E 814 |
2 hr. |
2 hr. |
2 hr. |
2 hr.* |
2 hr. |
3MU/DI 120-01 |
ISO 6944 (1985) Duct A |
ASTM E 814 |
1 hr. |
1 hr. |
1 hr. |
1 hr.* |
1 hr. |
3MU/DI 60-01 |
ASTM E 2336 |
Reference Design listing |
3MU/FRD 120-18
3MU/FRD 120-19
|
ICC-ES AC 101 |
Noncombustibility Test (ASTM E 136) – Pass
Fire Resistance Test (ASTM E 119) – 2 hr
Durability Test (ASTM C 518 modified) – Pass
Internal Fire Test – 4 hr @ 500°F and 30 minutes @ 2000°F – Pass
Fire-Engulfment Test (ASTM E 119 Exposure) – 2 hr |
3MU/FRD 120-18
3MU/FRD 120-19
|
Test Standard |
Design No. |
CAN/ULC-S115 |
3MU/PF 60-01 |
CAN/ULC-S115 |
3MU/PF 120-01 |
CAN/ULC-S115 |
3M/PH 120-09 |
CAN/ULC-S115 |
3M/PH 120-16 |
CAN/ULC-S115 |
3M/PHV 120-02 |
CAN/ULC-S115, ASTM E814 |
3M/PHV 120-03 |
CAN/ULC-S115, ASTM E814 |
3M/PHV 120-04 |
CAN/ULC-S115 |
3M/PHV 120-07 |
CAN/ULC-S115 |
3M/PHV 120-08 |
CAN/ULC-S115, ASTM E814 |
3M/PHV 120-10 |
CAN/ULC-S115 |
3M/PHV 120-12 |
CAN/ULC-S115, ASTM E814 |
3M/PHV 120-15 |
CAN/ULC-S115 |
3M/PV 60-02 |
CAN/ULC-S115, ASTM E814 |
3M/PV 120-01 |
CAN/ULC-S115 |
3M/PV 120-02 |
CAN/ULC-S115 |
3M/PV 120-03 |
CAN/ULC-S115 |
3M/PV 120-04 |
CAN/ULC-S115 |
3M/PV 120-06 |
CAN/ULC-S115 |
3M/PV 120-07 |
CAN/ULC-S115 |
3M/PH 60-04 |
Note: See Design Listings for Ratings
*Note: T-Rating is zero for installation through a fire-rated shaft wall with insulated duct on outside of fire-rated shaft assembly and un-insulated duct on the inside of the shaft assembly, and when the fire exposure is from the side with the insulated duct.