FIRE RESISTANT PRODUCTS & COMPONENTS
DOORS - ROLLING STEEL
Accordion Fire Door System, Series AC8000. May incorporate vision panels. May contain integral proprietary swing doors. For installation in gypsum wall or masonry construction.
Alternate Bi-Parting Door Configuration: An alternate bi-parting door configuration consisting of a McKeon Series S4000, S9000 and S7000 Side Coiling and Side Acting Steel Fire Door and a McKeon Series AC8000 Accordion Fire Door is allowed. The McKeon Door Series with the most stringent restrictions and limitations, including size, will be applied for this alternate bi-parting door configuration.
Rating - Maximum 3 Hours
AIR LEAKAGE RATINGS
Test Standard |
Test Type |
Ratinga, b |
UL 1784 |
Ambient Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
UL 1784 |
Elevated Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
aThese assemblies were evaluated without the use of an artificial bottom seal. When installed with the manufacturer-provided brushes and sweeps, they may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC. For installations exclusive of hoistway opening protection and lobby doorways, and where pressurization is not used to control smoke movement, seals at the bottom edges of the assemblies are optional.
SIZE LIMITATIONS
Certification Procedure |
Maximum Area |
Maximum Width |
Maximum Height |
LABEL |
130 sq ft |
13'-0" |
10'-0" |
CERTIFICATE/LABEL |
unlimited* |
unlimited* |
unlimited* |
*The AHJ may approve "oversize" doors with no size limitation based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size.
CODE COMPLIANCE RESEARCH REPORT
Evaluation Method |
Building Code |
CCRR Number |
NFPA 252
UL 10B
UL 1784 |
2021, 2018, and 2015 IBC
2021, 2018, and 2015 IFC
2023, 2020 FBC
2022 CBC
2023 LABC |
CCRR-1086 |