FIRE RESISTANT PRODUCTS & COMPONENTS
DOORS - ROLLING STEEL
Product Covered
Series T2000/T5000/TU5000*.
Product Description
Non-insulated: Vertical rolling steel fire door assembly with integral swinging doors for installation in gypsum and structural steel stud, gypsum-protected CLT (see limitations below), or masonry construction. May incorporate vision panels.
Fire Resistance Rating: 3 Hour
Insulated: Vertical rolling steel fire door assembly with integral swinging doors for installation in gypsum and structural steel stud, gypsum-protected CLT (see limitations below), or masonry construction. May incorporate vision panels.
Fire Resistance Rating: 3 Hour
Temperature Rise Ratings:
- 650 degree Fahrenheit maximum temperature rise rating at 30 minutes when used singly in a masonry, gypsum-protected CLT (see limitations below), or drywall and structural steel stud opening.
- Please note, if an Integral Proprietary Swinging Door is used in conjunction with the McKeon Series T2000, T5000 or TU5000 Vertical Rolling Steel Fire Doors, the integral swinging doors must also bear a temperature rise rating equal to or better than the respective temperature rise ratings noted above.
- Fire Resistance Rating: 90 Minutes (Unit Used Singly)
*TU5000 pair swinging doors require 4 point latching.
AIR LEAKAGE RATINGS
Test Standard |
Test Type |
Ratinga |
UL 1784 |
Ambient Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
UL 1784 |
Elevated Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
aThese assemblies were evaluated without the use of an artificial bottom seal. When installed with the manufacturer-provided brushes and neoprene bottom seal, they may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC. For installations exclusive of hoistway opening protection and lobby doorways, and where pressurization is not used to control smoke movement, seals at the bottom edges of the assemblies are optional.
CODE COMPLIANCE RESEARCH REPORT
Evaluation Method |
Building Code |
CCRR Number |
NFPA 252
UL 10B
UL 1784 |
2021, 2018, and 2015 IBC
2021, 2018, and 2015 IFC
2023, 2020 FBC
2022 CBC
2023 LABC |
CCRR-1086 |
SIZE LIMITATIONS
Certification Procedure |
Maximum Area |
Maximum Width |
Maximum Height |
LABEL |
156 sq ft |
13'-0" |
12'-0" |
CERTIFICATE/LABEL |
unlimited* |
unlimited* |
unlimited* |
*The AHJ may approve "oversize" doors with no size limitation based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size.
INSTALLATION LIMITATIONS
Assemblies may be installed in gypsum with structural steel stud, masonry, or gypsum-protected Cross Laminated Timber (CLT) walls. When installed in gypsum-protected CLT walls, the following conditions apply:
- Supporting CLT wall must be fire-resistance-rated in accordance with the code.
- Noncombustible protection shall be in accordance with the code, but not less than:
- Two layers of 5/8-inch Type X gypsum per face for walls required to have a fire-resistance rating of 2 hours or less.
- Three layers of 5/8-inch Type X gypsum per face for walls required to have a fire-resistance rating of 3 hours or more.
- Assemblies bearing a fire-protection rating of 90 minutes or less shall be designed with an additional sacrificial 1 inch of anchorage embedment depth or be through-bolted.
- Assemblies bearing a fire-protection rating of 2 or 3 hours shall use through-bolted anchorage.