National Custom Hollow Metal Fire Doors Series DH, DP, DSB, DST-6 & DST-8
Company: National Custom Hollow Metal Doors and Frames
DOORS:
Hollow Metal Type (16, 18 gauge) (Steel-Faced), (Stainless Steel Singles or Standard Pairs Neutral Pressure Only) (DP Series*) (Foam Filled), Swinging Flush Design Fire Door for installation single swing, pairs, or double egress in up to 1-1/2 hour locations.
Limitations: Active Leaf - Single Point Latch or Fire Exit Hardware/Inactive Leaf - Top and Bottom Bolts or Concealed/Surface Mounted Vertical Rod Fire Exit Hardware/Astragal required on pairs over 20 minutes including DE/Viewer/Maximum Size
Glass Lights - 1296 sq. In. per door or to the maximum size allowed by Listed fire rated vision kit and Listed fire rated glazing following their procedures with steel channel. Double Egress Doors - Concealed/Surface Mounted Vertical Rod Fire Exit Hardware required on each door, top and bottom latching.
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
Standard Pairs - 8'0" wide x 8'0" high
Double Egress - 8'0" wide x 8'0" high (Each leaf maximum 4'0" wide)
Double Egress not allowed in stainless steel. |
Hollow Metal Type (16, 18 gauge) (Stainless Steel [Single or Standard Pair ] or Carbon Steel-Faced [Single Swing, Pairs, Double Egress]) (DH Series*) (Paper Honeycomb Filled), Swinging Flush Design Fire Door for installation in single swing in up to 3 hour locations and standard pair/double egress in up to 1-1/2 hour locations.
Limitations: Active Leaf - Single Point Latch or Fire Exit Hardware/Inactive Leaf - Top and Bottom Bolts or Concealed/Surface Mounted Vertical Rod Fire Exit Hardware/Astragal required on pairs over 20 minutes including DE/Viewer/Maximum Size Glass Lights: 3 hours - 100 sq. in.; 1-1/2 hours 3/4 hour and 20 minutes - 1,296 sq. in. or to the maximum size allowed by Listed fire rated vision kit and Listed fire rated glazing following their procedures with steel channel. Double Egress Doors - Concealed/Surface Mounted Vertical Rod Fire Exit Hardware required on each door, top and bottom latching.
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
Standard Pairs - 8'0" wide x 8'0" high
Double Egress - 8'0" wide x 8'0" high (Carbon Steel Only)
(For pairs and DE, each leaf maximum 4'0" wide.)
Double egress not allowed in stainless steel. |
Hollow Metal Type (16, 18 gauge) (Steel-Faced) (DST-6 Series*) (Steel-Stiffened), Swinging Flush Design Fire Door for installation in up to 3 hour locations.
Limitations: Active Leaf - Single Point Latch or Fire Exit Hardware/Inactive Leaf - Top and Bottom Bolts or Concealed/Surface Mounted Vertical Rod Fire Exit Hardware/Astragal required on pairs/Singles and Pairs - Louver or Glass Light/Maximum Size Glass Light: 3 hour - 100 sq. in.; 1-1/2 hours, 3/4 hour and 20 minutes - 1,296 sq. in. or to the maximum size allowed by Listed fire rated vision kit and Listed fire rated glazing following their procedures. Dutch Doors require Astragal on Top Leaf and Single Point Latch on both Top and Bottom Leaf.
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
Pairs - 8'0" wide x 8'0" high (Each leaf maximum 4'0" wide)
Dutch Door - 3'6" wide x 8'6" high (Each leaf maximum 3'9" high) |
Hollow Metal Type (16, 18 gauge) (Steel-Faced) (DSB Series*) (Steel-Stiffened), Swinging Flush Design Fire Door for installation in up to 1-1/2 hour locations.
Limitations: Active Leaf - Single Point Latch or Fire Exit Hardware/Inactive Leaf - Top and Bottom Bolts or Concealed/Surface Mounted Vertical Rod Fire Exit Hardware/Astragal required on pairs/Viewer/Singles and Standard Pairs - Louver or Glass Light/Maximum Glass Light/Maximum Glass Light:1-1/2 hours, 3/4 hour and 20 minutes - 1,296 sq. in. or to the maximum size allowed by Listed fire rated vision kit and Listed fire rated glazing following their procedures. Double Egress Doors - Concealed/Surface Mounted Vertical Rod Fire Exit Hardware required on each door.
| Maximum Size of Openings: |
Singles - 4'0" wide x 9'0" high
Pairs - 8'0" wide x 8'0" high (Each leaf maximum 4'0" wide)
Double Egress - 8'0" wide x 8'0" high (Each leaf maximum 4'0" wide) |
Hollow Metal Type (16, 18 gauge) (Steel-Faced) (DST-8 Series*) (Steel-Stiffened), Swinging Flush Design Fire Door for installation in up to 3 hour locations.
Limitations: Active Leaf - Single Point Latch or Fire Exit Hardware/Inactive Leaf - Top and Bottom Bolts or Concealed/Surface Mounted Vertical Rod Fire Exit Hardware/Astragal required on pairs/Viewer/Singles and Pairs - Louver or Glass Light/Maximum Size Glass Light: 3 Hour - 100 sq. in.; 1-1/2 hours, 3/4 hour and 20 minutes - 1,296 sq. in. or to the maximum size allowed by Listed fire rated vision kit and Listed fire rated glazing following their procedures.
| Maximum Size of Openings: |
Singles - 4'0" wide x 10'0" high (4'0" wide x 8'0" high with
fire exit hardware)
Pairs - 8'0" wide x 10'0" high (Each leaf maximum 4'0" wide)
(8'0" wide x 8'0" high with fire exit hardware; each leaf
maximum 4'0" wide). |
*Manufacturer's Designation.
Note: For additional information please refer to the G-P Gypsum Corp. listing on Steel-Faced Temperature Rise Door.
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)
CATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED:
Steel-Faced (16, 18 gauge) (Steel-Stiffened) (DSB/DST-6/DST-8) (Flush), Swinging Flush Door for installation in 1-1/2 hour locations. For use in listed (3-sided) 16 gauge welded steel frames meeting ANSI-A155.1/UL-63 or as per frame manufacturer's listing(s).
Limitations: Mortise or Cylindrical Latches with maximum 5" Backset/Mortise Exit Devices/Surface Mounted Vertical Rod Fire Exit Devices/Rim-Type Fire Exit Devices/Deadbolts/Surface Bolts/Automatic Flush Bolts/Surface-Mounted Closers/Surface-Mounted Protection Plates/Plant-Ons/Viewer/Surface-Mounted or Mortised Door Bottoms/Astragal Required/Temperature Rise - Greater than 650°F at 30 minutes.
|
Configuration
|
Maximum Size*
|
| Single Swing |
4'0" wide x 8'0" high |
| Standard Pairs |
8'0" wide x 8'0" high |
| Double Egress Pairs |
8'0" wide x 8'0" high |
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.
Testing Standards: UBC-7-2-97, UL-10C (Positive Pressure).
Evaluated to the following:
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C". See Positive Pressure Section Header for more information