McKEON FireFighter® Model D200 and D200E 3 Hour Fire & Smoke Barrier Company: McKEON Code Compliance Research Reports: CCRR-0455

McKEON FireFighter® Model D200 and D200E Curtain Assemblies are for use as fire and smoke barrier curtain assemblies when installed in a 3-hour steel stud/gypsum, gypsum-protected CLT (see limitations below), or masonry wall. Model D200 assemblies may contain curtain overlaps. Model D200E assemblies may contain overlaps and/or passage doors sealed with a hook & loop fastener. See below for ratings and limitations.

FIRE RATINGS
Test Standard Rating
UL 10D 180 minutes
UL 10B, UL 10C, NFPA 252 20 minutes without hose stream

AIR LEAKAGE RATINGS
Test Standard Test Type Ratinga, b
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
aThis assembly was evaluated without the use of an artificial bottom seal and may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC.
bA pair of two-inch brushes are required at the head of the curtain to meet air leakage ratings, a single one-inch brush at each side guide is optional based on test results.  Brushes must be listed & labeled for fire applications.

CODE COMPLIANCE RESEARCH REPORT
Evaluation Method Building Code CCRR Number
UL 10B
UL 10C
UL 10D
UL 1784
2021, 2018, & 2015 IBC
2021, 2018, & 2015 IFC
2023, 2020 FBC
2022 CBC
2023 LABC
2021, 2018 NFPA 101
CCRR-0455

MAXIMUM SIZE LIMITATIONS
Certification Procedure Maximum Area Maximum Width Maximum Height
LABEL (with overlap) 93.44 sq ft 9'-8" 9'-8"
LABEL (without overlap) 143 sq ft 13'-0" 11'-0"
CERTIFICATE/LABEL  unlimited* unlimited* unlimited*
*Assemblies exceeding these dimensions must have an oversize label, issued by Intertek, stating the assembly is constructed in accordance with the certified design except for size. Acceptance of the oversize assembly is at the discretion of the Authority Having Jurisdiction.

MINIMUM SIZE LIMITATIONS (UL 1784 ONLY)*
Width Height
7' 0" 7' 0"
*Fire-only assemblies do not have a minimum size.

INSTALLATION LIMITATIONS
Assemblies may be installed in gypsum with structural steel stud, masonry, or gypsum-protected Cross Laminated Timber (CLT) walls. When installed in gypsum-protected CLT walls, the following conditions apply:
  • Supporting CLT wall must be fire-resistance-rated in accordance with the code.
  • Noncombustible protection shall be in accordance with the code, but not less than:
    • Two layers of 5/8-inch Type X gypsum per face for walls required to have a fire-resistance rating of 2 hours or less.
    • Three layers of 5/8-inch Type X gypsum per face for walls required to have a fire-resistance rating of 3 hours or more.
  • Assemblies bearing a fire-protection rating of 90 minutes or less shall be designed with an additional sacrificial 1 inch of anchorage embedment depth or be through-bolted.
  • Assemblies bearing a fire-protection rating of 2 or 3 hours shall use through-bolted anchorage.

Minimum Curtain Overlap (when present): 23-5/8"
Minimum Bottom Bar weight: 0.30 lbs per sq. ft. of curtain area
Maximum Curtain Rivet spacing: 15" on-center
Maximum Hook & Loop length: 8' 0"
Stainless Steel Hook & Loop required for fire applications
Side Guide anchorage: 1/4" anchors spaced maximum 18" on-center
Top Hood/Assembly mounting: maximum 40" on-center
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationMarch 21st, 2016
Certificate NumberWHI16–20384301
CriteriaUL 10(c) (2009)
CriteriaUL 10(b) (2008) (R2009)
CriteriaUL 10(d) (2009)
CriteriaUL 1784 (2015)
CriteriaNFPA 252 (2017)
CSI Code08 30 00 Specialty Doors and Frames
Listing SectionSMOKE CONTROL DOOR ASSEMBLIES
Spec ID29655