3M Fire Barrier Duct Wrap 615+ Company: 3M Company

This specification covers 3M Fire Barrier® Duct Wrap 615+ and 3M Fire Barrier Duct Wrap Collar 615+ products.

PRODUCT DESCRIPTION
The 3M Fire Barrier® Duct Wrap 615+ and 3M Fire Barrier Duct Wrap Collar 615+ are nominal 6-pcf blanket that is encapsulated on all sides with a polypropylene/scrim/foil or an aluminized polyester/scrim/foil material. The 3M Fire Barrier® Duct Wrap 615+ blanket is a high-temperature body-soluble fiber that utilizes a spinning technology to create a fiber with thermal and mechanical properties. This fiber is made from a blend of calcium, silica and magnesium having the ability to support maximum temperatures up to 1200°C. 3M Fire Barrier® Duct Wrap 615+ products are produced in an ISO-9002-certified facility where bulk, double-needled blanket and modules are manufactured. The 3M Fire Barrier® Duct Wrap 615+ family of products can be used in a variety of applications including refractory linings, thermal insulation, metals transfers and fire protection. Reference the Intertek Third Party Quality Control Manual located in the Quality Control Tab of this listing for further specifications.
Only the thickness and density of the materials designated in Intertek Product and Design Listings are certified. 
 
RATINGS
 
 
Standard Rating Design Number
ISO 6944 (1985) Duct A only 1 hour
(Stability, Insulation, and Integrity)
3MU/DI 60-01
ASTM E 814 ·      F-Rating – 1 hour
·      T-Rating – 1 hour*
ISO 6944 (1985) Duct A only 2 hour
(Stability, Insulation, and Integrity)
3MU/DI 120-01
ASTM E 814 ·    F-Rating – 2 hour
·    T-Rating – 2 hour*
ASTM E 2336
and
ICC-ES AC101
·     Noncombustibility (ASTM E 136): Pass
·     Fire Resistance (ASTM E 119): 2 hour
·     Durability (ASTM C 518 modified): Pass
·     Internal Fire Test: 4 hr @ 500°F and 30 minutes @ 2000°F – Pass
·    Fire-Engulfment Test (ASTM E 119 Exposure) – 2 hour
3MU/FRD 120-18
ASTM E 2336
and
ICC-ES AC101
·     Noncombustibility (ASTM E 136): Pass
·     Fire Resistance (ASTM E 119): 2 hour
·     Durability (ASTM C 518 modified): Pass
·     Internal Fire Test: 4 hr @ 500°F and 30 minutes @ 2000°F – Pass
·    Fire-Engulfment Test (ASTM E 119 Exposure) – 2 hour
3MU/FRD 120-19
ICC-ES AC101 (2001) Section 4.5 Fire-Engulfment 2 hour 3MU/FRD 120-10
ICC-ES AC101 (2001) Section 4.5 Fire-Engulfment 2 hour 3MU/FRD 120-11
CAN/ULC S144 Internal Fire Test -Pass;
Fire Engulfment Test - 2 hour fire rating
3MU/BI 120-03
ASTM E814 F-Rating - 120 Minutes
T-Rating - 120 Minutes
3MU/BI 120-04
CAN/ULC-S115 F, FT-Rating - 120 Minutes
FH, FTH-Rating - 120 Minutes
3MU/BI 120-04
ASTM E814 F-Rating - 120 Minutes
T-Rating - 120 Minutes
3MU/BI 120-05
CAN/ULC-S115 F, FT-Rating - 120 Minutes
FH, FTH-Rating - 120 Minutes
3MU/BI 120-05
ASTM E2816 Rating - 60 Minutes Condition D 3MU/DI 60-03
ASTM E814 F-Rating - 60 Minutes
T-Rating - 60 Minutes
3MU/DI 60-03
*Note: T-Rating is zero for installation through a fire-rated shaft wall with insulated duct on outside of fire-rated shaft assembly and un-insulated duct on the inside of the shaft assembly, and when the fire exposure is from the side with the insulated duct.

Certified Products can be identified by the Omega Point Laboratories (OPL), Warnock Hersey (WH), or ETL Certification Mark
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationJanuary 24, 2013
Certificate NumberWHI13 - 20265303
CriteriaISO 6944 (1985)
CriteriaASTM E136 (2004)
CriteriaASTM C518 (2004)
CriteriaASTM E2336 Sections 5.4 and 5.5 (2004)
CriteriaASTM E2336 Section 16.5 (2004)
CriteriaICC-ES AC101 Section 4.5 (2001)
CriteriaASTM E2336 (2016)
CriteriaASTM E2816 (2018)
CriteriaCAN / ULC S115 (2011)
CriteriaASTM E814 (2011a)
CriteriaASTM E119 (2012)
CriteriaASTM E136 (2011)
CriteriaCAN / ULC S144 (2012)
CriteriaASTM E814 (2013a)
CriteriaASTM E814 (2008b)
CriteriaASTM E136 (2009)
CriteriaASTM E119 (2010)
CriteriaASTM E814 (2010)
CriteriaASTM E119 (2010b)
CriteriaASTM C518 (2010)
CriteriaICC-ES AC101 Section 4.4 (2001)
CriteriaASTM E2336 Section 16.4 (2004)
CriteriaASTM E119 (2008a)
CriteriaASTM E2336 Section 15 (2004)
CriteriaASTM E2336 (2004)
CriteriaICC-ES AC101 (2001)
CSI Code23 00 00 Heating, Ventilating, and Air Conditioning (HVAC)
CSI Code07 21 16 Blanket Insulation
CSI Code23 07 13 Duct Insulation
Listing SectionFIRE RESISTANT DUCT
Listing SectionFIRESTOP SYSTEMS
Spec ID29729
Design Documents
Public Documents
No Results