Viega PureFlow PEX and Viega PureFlow System are cross-linked polyethylene tubing for use in hot and cold water distribution applications.
FLAME SPREAD RATINGS
Test Standard |
Product Tested |
Flame Spread |
Smoke Development |
ASTM E84 |
3/8" to 2" Viega PureFlow PEX with insulation |
<25 |
<50 |
ASTM E84 |
3/8" to 1" Viega PureFlow System with insulation |
<25 |
<50 |
CAN/ULC-S102.2 |
3/8" to 2" Viega PureFlow PEX with insulation |
<25 |
<50 |
CAN/ULC-S102.2 |
3/8" to 1" Viega PureFlow System with insulation |
<25 |
<50 |
CAN/ULC-S102.2 |
3/8" to 1/2" Viega PureFlow PEX without insulation |
<25 |
<50 |
CAN/ULC-S102.2 |
3/8" to 1/2" Viega PureFlow System without insulation |
<25 |
<50 |
Insulated product ratings apply only when tubing is field insulated with fiberglass insulation conforming to the following:
· ASTM E84 Listed
· Flame Spread Index of < 25
· Smoke Developed Index of < 50
· Wall thickness – minimum 1/2”
· There shall be no exposed tubing. Tubing may contain fittings which shall also be fully encased in insulation.
FIRE RATINGS
Test Standard |
Products Covered |
Rating |
Design Number |
ASTM E119
CAN/ULC-S101
UL 263
NFPA 251
UBC 7-1 |
3/8" to 2" Viega PureFlow PEX with insulation
3/8" to 1" Viega PureFlow System with insulation |
1-Hour |
VL/FWDP 60-01 |
ASTM E119
CAN/ULC-S101
UL 263
NFPA 251
UBC 7-1 |
3/8" to 2" Viega PureFlow PEX with insulation
3/8" to 1" Viega PureFlow System with insulation |
1-Hour |
VL/FWDP 60-02 |
ASTM E119
CAN/ULC-S101
UL 263
NFPA 251
UBC 7-1 |
3/8" to 2" Viega PureFlow PEX with insulation
3/8" to 1" Viega PureFlow System with insulation |
2-Hour |
VL/FWDP 120-01 |
ASTM E814
CAN/ULC-S115 |
3/8" to 2" Viega PureFlow PEX with insulation
3/8" to 1" Viega PureFlow System with insulation |
2-Hour |
VL/FWDP 120-02 |