Rogue 20 Min With Hose Stream Panel Type Door Company: Rogue Valley Door

PRODUCT COVERED

20 Minute Panel Type Door

 

PRODUCT DESCRIPTION

Panel-design wood fire door using MDF core and proprietary mineral stile and rail systems, Single-Swing or Pairs,

 

SIZE LIMITATIONS

 

Single Swing

Maximum Width             3’6”

Maximum Height            8’0”

Minimum Thickness       1-3/4” ± 1/16”

 

Standard Pairs

Standard Pairs require a minimum of 3-point latching

Maximum Width             7’0”

Maximum Height            8’0”

Minimum Thickness       1-3/4” ± 1/16”

 

Double Egress

Not Allowed

 

EVALUATED TO THE FOLLOWING

 

This category includes doors evaluated without an edge-sealing system between the door and frame.  It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.  Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.

 

These doors are eligible for use in any "Category C - Standard" frame.  These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing. All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.

 

All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C". See Positive Pressure Section Header for more information.

Listing Report Return to Search
Attributes
CriteriaASTM E152-81a
CriteriaUL 10(c) (1998)
CriteriaUBC 7-2 (1997)
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaASTM E2074 (2000)
CriteriaNFPA 252 (2003)
CriteriaCAN / ULC S104 (1980) (R1985)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min w/Hose Negative Pressure
Fire Resistance20 Min w/Hose Positive Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID29944
SwingSingle Swing
SwingStandard Pairs