Cookson Company Fire Doors & Service Counter Fire Doors Company: Cookson Company, Inc. (The)

DOORS - ROLLING STEEL
 
Vertical Rolling, Steel Fire Door and Guide Assembly for installation in concrete, masonry, structural steel or gypsum board walls with 16 gauge minimum metal studs in 3 or 4 hour locations (May be furnished with Approved Gasketing Material for Smoke & Draft Control Rating) (Model Nos. FD, FD1, FD2, FD3, FD4, FD5, FDWI Series)*.
 
Limitations: Limited to 3/4 hour locations when installed with a 6" wide x 1" high Light.
 
Maximum Size of Openings: 13'6" wide x 12'0" high.
    
Vertical Rolling, Steel Service Counter Fire Door for installation in concrete, masonry, structural steel or gypsum board walls with 16 gauge minimum metal studs in 1-1/2 hour locations (May be furnished with Approved Gasketing Material) for Smoke & Draft Control Rating (Model No. FD10)* (May be furnished with optional stainless steel trim).
 
Maximum Size of Openings: 8'0" wide x 10'0" high.
Maximum Size with "S" Label: 16'0" wide x 12'0" high
 
Limitations: Limited to 3/4 hour locations when installed with a 6" wide x 1" high Light.
 
Vertical Rolling, Steel Service Counter Fire Door for installation in concrete, masonry, structural steel in 3 hour locations (May be furnished with Approved Gasketing Material) for Smoke & Draft Control Rating (Model No. FD10)* (May be furnished with optional stainless steel trim).
 
Maximum Size of Openings: 12'0" wide x 8'6" high. (50 sq ft Max)
Maximum Size with "S" Label: 16'0" wide x 12'0" high
  
Limitations: Limited to 3/4 hour locations when installed with a 6" wide x 1" high Light.
 
*Manufacturer's Designation, May be changed to "SD-10" when used with "S" label (For Smoke & Draft control rating).

Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:

CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies

and are installed in accordance with the following:
NFPA-80, Fire Doors & Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Products)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)

COUNTERTOPS FOR USE WITH VERTICAL ROLLING DOORS 
Mineral Core (HPL Laminated Surfaces), 1-1/2" thick Countertop for use with listed Vertical Rolling Fire Doors in 20 minute, 3/4 hour, 1 hour and 1-1/2 hour locations.
Maximum Length of Countertop: 9'0"
Maximum Width of Opening: 8'0"
 
Pressed Steel (Cold-Rolled or Stainless) (14 gauge) Countertop for use with listed Vertical Rolling Fire Doors in 20 minute, 3/4 hour, 1 hour and 1-1/2 hour locations.
Maximum Length of Countertop: 4'0"
Maximum Width of Opening: 3'0"
 

DOORS WITH OVERSIZE CERTIFICATES (No Fire Rating) 

Doors Mounted to 1 or 2 Hour Drywalls
Oversize Certificate: Maximum of 1-1/2 hour location.

1. Model "FD" Series and "FDWI" Series
Maximum of 1-1/2 hour location
Maximum Width:  36’–6”
Maximum Height:  24’–0”
Maximum Area:  876 sq. ft.

2. Model "FD-10" Series
Maximum of  1-1/2 hour exposure
Maximum Width: 16' -0"
Maximum Height: 12' -0"
Maximum Area: 192 sq.ft.

Doors Mounted to 3 hour Concrete, Concrete Block,
Masonry Unit, or Structural Steel Jambs Walls
Oversize Certificate: Maximum of 3 hour location
 
1. Model “FD10” Series
Maximum Width:  16’–0”
Maximum Height:  12’–0”
Maximum Area:  192 sq. ft.
Doors Mounted to 4 hour Concrete, Concrete Block,
Masonry Unit, or Structural Steel Jambs Walls
Oversize Certificate: Maximum of 4 hour location
 
1. Model “FD” Series and “FDWI” Series
Maximum Width:  36’–6”
Maximum Height:  24’–0”
Maximum Area:  876 sq. ft.
Listing Report Return to Search
Attributes
CriteriaNFPA 252 (2008)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 1784 (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 30 00 Specialty Doors and Frames
CSI Code08 36 00 Panel Doors
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire Resistance60 Min Neutral Pressure
Fire Resistance20 Min Neutral Pressure
Fire Resistance4 Hour Neutral Pressure
Listing SectionCOUNTERTOPS FOR USE WITH VERTICAL ROLLING DOORS
Listing SectionDOORS - ROLLING STEEL