Construction Specialties Acrovyn® Door 8'6"x8' 20 Min Model "Pair w/ Hose" & 4'x8' 20 Min w/ Hose Model "Single Swing" Company: Construction Specialties, Inc.

PRODUCT TYPE & MODEL NOS.:
Particle Board, Stave Core, & Agrifiber Core, Swinging Flush Door for installation in up to 20 minute with hose stream locations.   For use in listed (3-sided) 16-gauge welded steel frames meeting ANSI A155.1/UL63 or as per frame manufacturer’s listing(s).   
Configuration Maximum Size Edge-Sealing System(s)
Single Swing*
 
 
 
 
 
 
 
 
 
 
 
Standard** Pairs
 
 
 
Double** Egress
4’0” x 8’0”
 
 
 
 
 
 
 
 
 
 
 
8'6" x 8'0"
(4'3" Max. Width per Leaf)
 
8'6" x 8'0"
(4'3" Max. Width per Leaf)
PVC encased Palusol dadoed into top rail only. Alternate intumescent for top rail: Technofire 2000 1.3 mm full width across entire length of top rail 
PVC encased Palusol dadoed into the top rail of each leaf. Alternate intumescent for top rail: Technofire 2000 1.3 mm full width across entire length top rail each leaf.
Palusol concealed behind the replaceable edge on each stile on each leaf
 
Note*: SINGLE SWING - Maximum width may be increased to 4'3" when Wide Door stile is used (refer to Figure 05 of Manufacturing section)
 
Note**: Wide door stile must be used for Maximum width of 8'6" for pairs, refer to Manufacturing Section.
 
Double egress doors requires 4-point latching
 
Limitations*:
Cylindrical Latches with maximum 5" backset / Mortised Latchsets / Surface Mounted Vertical Rod fire exit device / Rim Type fire exit device / Less Bottom Rod** fire exit device / Deadbolts / Surface Bolts / Automatic Flush Bolts / Extension Bolts 18" Max. / Surface Mounted Door Bottoms / Mortised Door Bottoms / Vision Lite Kit - Maximum 1296 sq. in. / Surface Mounted Closers / Electric Raceways / Surface Mounted Protection Plates / Viewer / Fire Latch.
 
 
* See manufacturer’s installation instructions for additional information on Smoke and Draft Control, size restrictions, and limitations.
**With Hose Stream:  door to floor.
   Without Hose Stream:  door to door.
Evaluated to the following... 
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
Listing Report Return to Search
Attributes
CriteriaCAN4 S104 (1985)
CriteriaNFPA 252 (2008)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance20 Min w/Hose Stream PP Cat A Door
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID30000
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents
No Results