Wood Core Type, Raised Panel Design (Proprietary Construction), Swinging Fire Door for installation in pairs 20 minute locations (without hose stream test).
Limitations
Preassembled, Mortised or Cylindrical Latches with up to a 2-3/4" backset/Deadbolts/Rim Type Fire Exit Hardware/Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted or Flush, Automatic or Manual Bolts with a maximum extension of 24"/Viewer/Surface Mounted Closers/Surface Mounted or Automatic Door Bottoms/Vision Panel - maximum 1,040 sq.in.
Maximum Size
8'0" wide x 9'0" high
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)