Curries 20-180 Min Hollow Metal Fire Doors Model 747
Company: Curries Company
Hollow Metal Type (14, 16, 18 gauge) (Steel-Faced) (Vertically-Stiffened), Swinging Flush Design Fire Door for installation singly or in single Dutch Doors in 20 minute through 3 hour locations.
Nominal Door Thickness: 1-3/4", minimum
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised Automatic or Surface Mounted Manual Top and Bottom (Flush) Bolts/Lights - 100 in2/Louvers - 24" x 24" (45 and 90 minutes only)/Insulation permitted*.
| Maximum Size of Openings |
| Singles: |
4’-0” wide by 10’-0” high |
| Single Dutch Door: |
3’-8” wide by 7’-2” high |
* 450°F Temperature Rise option available. Standard configuration is >650°F.
Hollow Metal Type (14, 16, 18 gauge) (Steel-Faced) (Vertically-Stiffened), Swinging Wicket Design Fire Door for installation singly in 20 minute through 45 minute locations.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" backset/Minimum one Deadlock for Inner Wicket Door/Protection Plate/Raceway/Door Position Switch/Lights - 216 in2/Fiberglass Insulation Permitted/Astragal (4-Sided) Required Around Outer Entry Door and Inner Wicket Door Interface.
| Maximum Size of Openings |
| Singles – Outer (Entry) Door: |
4’-0” wide by 7’-2” high |
| Singles – Inner Large Wicket Door: |
2’-10” wide by 5’-2” high |
| Singles – Inner Small Wicket Door: |
17” wide by 17” high |
| Door Thickness (Entry and Access Door): |
1-3/4” ±1/16” |
| Single Dutch, Standard/Double Egress Pairs: |
Not Allowed |
Hollow Metal Type (14, 16, 18 gauge) (Steel-Faced) (Vertically-Stiffened), Swinging Flush Design Fire Door for installation in pairs in 20 minute through 3 hour locations. Astragal is optional on 1-1/2 hour or less pair.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised Automatic or Surface Mounted Manual Top and Bottom (Flush) Bolts/Lights - up to 100 in2/Louvers – 24” x 24” (45 and 90 minutes only)/Insulation permitted*.
| Maximum Size of Openings |
| Pairs: |
8’-0” wide by 10’-0” high
(4’-0” wide by 10’-0” high each leaf) |
* 450°F Temperature Rise option available. Standard configuration is >650°F.
Maximum Door Sizes for Adams Rite Hardware and any Hardware Listed up to 10’ High**:
| Configuration |
Maximum Size |
| Single: |
4'-0" wide by 10'-0" high (up to 3 hour)
5'-0" wide by 10'-0" high (up to 1-1/2 hour) |
| Standard Pairs: |
8'-0" wide by 10'-0" high (up to 3 hour)
10'-0" wide by 10'-0" high (up to 1-1/2 hour) |
| Double Egress: |
8'-0" wide by 10'-0" high (up to 3 hour)
10'-0" wide by 10'-0" high (up to 1-1/2 hour) |
**Latchsets and Exit Devices for door leaves exceeding 4’ in width must fall within the approved general hardware limitations of this listing for the applicable door configuration. Hardware that is not explicitly specified for use with door leaves exceeding 4’ in width shall be used at the discretion of the AHJ.
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
- CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
- NFPA-252, Standard Methods for Fire Tests of Door Assemblies
- UL-10B, Fire Tests of Door Assemblies
- UL-10C, Positive Pressure Fire Tests of Door Assemblies
and are installed in accordance with the following:
- NFPA-80, Fire Doors and Windows
- Manufacturer's Instructions.