Mineral Core Type, (Wood Faces) (simulated Recessed Wood Panel), Swinging Fire Door for installation in singly or in pairs in 1 hour locations.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Deadbolt/Mortised or Surface Mounted Automatic or Manual Top & Bottom (Flush) Bolts/Surface Mounted Vertical Rod Fire Exit Hardware/Mortised or Surface Mounted Rim Type Fire Exit Hardware.
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high Pairs - 8'0" wide x 8'0" high |
Wood Core Type (Particle Board or Wood Block), Swinging Flush, Dutch Design Fire Door for installation in single swing 20 minute locations.
Limitations: Unit, Mortise and Cylindrical Latches with up to a 5" backset.
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high |
Wood Core Type (Particle Board) (2-1/4" thick), Swinging Flush Design Fire Door for installation singly or in pairs in 20 minutes locations.
Limitations: Concealed Vertical Rod Fire Exit Devices for Singles or Both Leaves of Paired Openings/Lights - 1,296 sq.in./For Pairs (without Hose Stream) one leaf may use Concealed Vertical Rod Fire Exit Device and the other leaf may use single point mortise exit device in combination with an open back strike/FRAME MUST BE GASKETED.
| Maximum Size of Openings: |
Singles - 4'0" wide x 9'0" high Pairs - 8'0" wide x 9'0" high |
Testing Standards: Tested per BOCA Basic/National, SBC, UBC requirements.