Intertek Directory of Building Products

Frameworks Mfg. 45 Min. Extruded Aluminum Fire Door Frame NP Company: Frameworks Manufacturing, Inc.

Extruded Aluminum Door Frame (Altura 2*) for installation singly or in pairs in 3/4 hour locations in steel/wood stud drywall openings.
Limitations:
Screws through faces or frame must be 6" o.c., maximum for 3/4 hour locations or 12" o.c., maximum for 20 minute locations.

Maximum Size of Openings: Singles: 3'0" wide x 9'0" high
Pairs: 6'0" wide x 9'0" high
Maximum Overall Dimension: Singles: 39" wide x 109-1/2" high
Pairs: 75" wide x 109-1/2" high


*/** - Manufacturer's designation

Evaluated to the following:

Unless otherwise noted, assemblies in this section have been tested to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies;
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies;
NFPA-252, Standard Methods of Fire Tests of Door Assemblies;
UBC-7-2-94, Uniform Building Code;
UL-10(b), Fire Tests of Door Assemblies;
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.

Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All frames are identified by either a label or embossed marking bearing the wording "Listed (Product)" and the WHI Certification Mark. Frames rated for less than 3 hours also bear the time interval. Frame labels that do not include a time interval are rated for 3 hours.

Listing Report Return to Search
Attributes
CriteriaNFPA 80 (1999)
CriteriaASTM E152-81a
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaNFPA 252 (1999)
CriteriaCAN / ULC S104 (1980) (R1985)
CriteriaUL 10(b) 2008 (R2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CSI Code08 11 16 Aluminum Doors and Frames
Fire Resistance20 Min NP Fire Doorframe
Listing SectionDOOR FRAMES
Spec ID30248
SwingSingle Swing
SwingStandard Pairs
Design Documents
No Results
Public Documents
No Results