Gulfport Industries 45/90 Min & 3 Hour Hollow Metal Fire Doors
Company: Gulfport Industries, Inc. (FL)
Hollow Metal Type (20 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door with Transom Panel for installation in single swing 1-1/2 hour locations.
Limitations: Mortise and Cylindrical Latches/Surface Mounted Rim Type Fire Exit Hardware.
Maximum Size of Openings: |
Singles - 3'0" wide x 7'2" high
Transom Panel - 2'8" wide x 3'0" high |
Hollow Metal Type (18 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation in single swing 1-1/2 hour locations.
Limitations: Mortise and Cylindrical Latches/Mortised and Surface Mounted Rim Type Fire Exit Hardware.
Maximum Size of Openings: |
Singles - 3'6" wide x 9'0" high |
Hollow Metal Type (18 gauge) (Paper Honeycomb Core) (Stainless Steel), Swinging Flush Design Fire Door for installation in single swing 1-1/2 hour locations.
Limitations: Mortise and Cylindrical Latches/Mortised and Surface Mounted Rim Type Fire Exit Hardware.
Maximum Size of Openings: |
3'0" wide x 7'2" high. |
Hollow Metal Type (20 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation singly or in pairs, including double egress in 1-1/2 hour locations when equipped with a listed single point latch.
Limitations: Cylindrical Latches/Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Top and Bottom Bolts.
Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
Pairs - 8'0" wide x 8'0" high
Double Egress - 8'0" wide x 8'0" high
Transom Panel - 8'0" wide x 2'0" high with Transom Bar |
Hollow Metal Type (20 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation singly or in pairs in 1-1/2 hour locations.
Limitations: Mortise and/or Cylindrical Latches/Mortised and Surface Mounted Rim Type Fire Exit Hardware/Mortised and Surface Vertical Rod Fire Exit Hardware/Mortised and Surface Mounted Top and Bottom Bolts.
Maximum Size of Openings: |
Pairs - 8'0" wide x 8'0" high, Astragal required |
Kalamein Type, Swinging Flush Design Fire Door for installation in single swing 1-1/2 hour locations.
Limitations: Cylindrical Latches.
Maximum Size of Openings: |
3'0" wide x 7'0" high |
Hollow Metal Type (20 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation in single swing 1-1/2 hour locations.
Limitations: Cylindrical Latches.
Maximum Size of Openings: |
3'0" wide x 7'0" high |
Hollow Metal Type (16, 18 gauge) (Steel-Stiffened) (Insulated or Paper Honeycomb Core), Swinging Flush Design Fire Door for installation singly or in pairs in 3 hour locations.
Limitations: Mortise and Cylindrical Latches/Mortised and Surface Mounted Top and Bottom Bolts.
Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
Pairs - 8'0" wide x 8'0" high, Astragal required |
Hollow Metal Type (20 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation singly or in pairs in 1-1/2 hour locations.
Limitations: Cylindrical Latches/Mortised and Surface Mounted Top and Bottom Bolts.
Maximum Size of Openings: |
Singles - 3'0" wide x 7'2" high
Pairs - 6'0" wide x 7'2" high, Astragal Required |
Note: For additional information please refer to the Pyrophobic Systems Ltd. listing.
Other Locations
Mississauga, ON
CANADA L4V 1P3.
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)