Wood Core Type (Particle Board or Wood Stave) Swinging Flush Design installation singly or in pairs, including double egress, in 20 minute locations.
Limitations:
Unit, Mortise, Card, combination, Interconnected or Cylindrical Latches with up to a 5" backset/deadbolts/lights - maximum 1,296 sq.in./Surface Mounted Vertical rod Fire Exit Hardware/Mortised or Surface Mounted Rim Type Fire Exit Hardware/Automatic door bottoms/Metal Edges or Fire Retardant treated edges required on pairs and double egress/SLM Edges on pairs or double egress do not require Metal Edges, SLM Edges may be rabbeted on pairs/pocket pivots/4" x 4" hinges/Mortised Automatic or Manual Top and Bottom Bolts/Overhead Concealed Closer Arms permitted/concealed closers/viewers/Metal Edge Guards/Surface Plates/Electric Raceways/Plant-Ons.
Maximum Size of Openings: |
Singles - 4'0" wide x 9'0" high or 3'0" wide x 10'0" high
Pairs - 8'0" wide x 9'0" high
Double Egress - 8'0" wide x 8'0" high |
Wood Core Type (Particle Board or Wood Stave) Swinging Flush Design Fire Door/Transom Panel Assembly for installation in single swing 20 minute locations.
Limitations:
Unit, Mortise, Card, Combination, Interconnected or Cylindrical Latches with up to a 5" backset/Deadbolts/Lights - maximum size 1,296 sq. in./Mortise or Surface Mounted Rim Type Fire Exit Hardware/Automatic Door Bottoms/Pocket Pivots/4" x 4" x 0.097" Hinges/Spring Bolts/Viewers/Electrical Raceways/Metal Edge Guards/Surface Plates/Plant-Ons/Rabbeted SLM Meeting Edges between Door and Transom Panel.
Maximum Size of Opening: |
Combination - 3'0" wide x 10'0" high max
Transom - 3'0" wide x 3'4" high max |
Wood Core Type (Particle Board or Wood Stave) Dutch Design, Swinging Flush Design Fire Door for installation in single swing 20 minute locations.
Limitations:
Unit, Mortise, Card, Combination, Interconnected, or Cylindrical Latches with up to a 5" backset/Deadbolt/Lights - maximum 1296 sq.in./Automatic Door Bottoms/Pocket Pivots/4" x 4" x 0.097" Hinges/Viewers/Metal Edge Guards/Surface Plates/Electrical Raceways/Plant-Ons/Top Leaf must have formed steel Astragal.
Maximum Size of Opening: |
4'0" wide x 8'0" high. |
Note: For additional information, please refer to the Weyerhaeuser - SLM Components and Georgia Pacific Corp. listings.
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)