Coopers Fire Ltd. 20 Minute to 90 Minute Fire Rated FireMaster Smoke and Fire Barrier (with or without Hook & Loop Fastened Passage) Company: Coopers Fire Ltd.

Coopers Fire Ltd. FireMaster Smoke and Fire Barrier (with or without Hook & Loop fastened passage) protective curtain assembly, FireMaster® Egress, for use in fire rated steel stud/gypsum or masonry wall applications.
Classification per UL 10D (90 Minute Fire Rating) with or without Hook & Loop and UL 10B, UL 10C, or NFPA 252 (20 Minute Without Hose Fire Rating). 
Maximum Size: 13' wide x  11' high (oversize certificates available)
Maximum Hook & Loop length: 8' 0"
Qualified per UL 10D (Fire) & UL 1784 (Smoke - brush type, number and length must be adhered to per test results)
UL 10B, UL 10C, NFPA 252 standards apply to 20 Minute Fire Endurance ratings without hose stream only.  Please note that acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationJuly 18, 2018
Certificate NumberWHI18 – 11025804
CriteriaUL 1784 (2004)
CriteriaUL 10(b) (2008)
CriteriaNFPA 252 (2008)
CriteriaUL 10(c) (2009)
CriteriaUL 10(d) (2009)
CriteriaNFPA 252 (2012)
CriteriaUL 10(d) (2014)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CSI Code08 30 00 Specialty Doors and Frames
Fire Resistance20 Min w/out Hose Negative Pressure
Fire Resistance90 Min Positive Pressure
Fire Resistance20 Min w/out Hose Positive Pressure
Listing SectionDOORS - ROLLING STEEL
Listing SectionSMOKE CONTROL DOOR ASSEMBLIES
Spec ID30311