Intertek Directory of Building Products

Smoke Guard® Model 2100 Company: Smoke Guard, Inc.

Products Covered:
Smoke Guard Model 2100 (M2100) Smoke and Smoke & Fire curtain assemblies.

Product Description:
The Smoke Guard M2100 systems consist of a filament glass fabric (identified as SGTex-10a, SGTex-10b, SGTex-10c, SGTex-30 or SGTex-32), which is wound onto a tube containing an internal drive system. Contained in a sheet metal housing, the curtain assembly is comprised of support rollers and associated electronics. The curtain edges are captured in vertical side guides during system deployment and the bottom edge of the curtain is attached to a weighted bottom bar. If the system encounters an alarm, the releasing device activates deploying the curtain. In the event of main power failure, an integrated battery system maintains the system.  Should main and backup power systems fail, the curtain will deploy in a controlled manner under the influence of gravity (Gravity Fail Safe). If required, wall switches are provided on each side of the curtain, allowing occupants to momentarily raise the curtain to egress. After the alarm condition clears, the curtain automatically rewinds into the housing.

The Smoke Guard M2100 system, utilizing any of the fabrics listed above, is recognized for use in smoke and draft control systems, as described in the tables below.
 
The Smoke Guard M2100 system, utilizing the SGTex-30 or SGTex-32 fabric, is additionally recognized for use in fire-resistance rated construction (as tested in accordance with UL10B, UL10C, UL10D and NFPA 252), as described in the tables below.

FLAME SPREAD RATINGS
Test Standard Flame Spread Smoke Development
ASTM E84 (All Fabrics) ≤ 25 ≤ 450
CAN/ULC S102 (SGTex-10c) 0 25
CAN/ULC S102 (SGTex-30) 0 20


AIR LEAKAGE RATINGS (With SGTex-10a, -10b, -10c, or -30 Fabric)
Test Standard Test Type Ratinga Size Restrictions
UL 1784 Ambient & Elevated Temperatures ≤3.0 cfm/ft2 at 0.10 in. of w.c. Min Area:19.5 ft2
Min Height: 3 ft
≤3.0 cfm/ft2 at 0.30 in. of w.c. Min Area:42.25 ft2
Min Height: 5.5 ft
aThis assembly was tested without an artificial bottom seal. The assembly may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC.

AIR LEAKAGE RATINGS (With SGTex-32 Fabric)
Test Standard Test Type Ratinga Size Restrictions
UL 1784 Ambient & Elevated Temperatures ≤3.0 cfm/ft2 at 0.10 in. of w.c. Min Area: 25 ft2
Min Height: 4.5 ft
≤3.0 cfm/ft2 at 0.20 in. of w.c. Min Area: 81.25 ft2
Min Height: 7.5 ft
aThis assembly was evaluated without an artificial bottom seal. The assembly may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC.

FIRE-RESISTANCE RATINGS (With SGTex-30 and SGTex-32)
Test Standard
Test Type
Fabric
Ratinga, b
UL 10D
Fire Endurance
SGTex-32
120 minutes
UL 10D Fire Endurance SGTex-30 180 minutes 
UL 10B, UL 10C, and NFPA 252
Fire Endurance
SGTex-32 or
SGTex-30
20 minutes without hose stream
aThe UL 10B, UL 10C, and NFPA 252 standards apply to 20 Minute Fire Endurance ratings without hose stream only.  Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.
bCurtains exceeding the tested dimensions of 10 ft x 10 ft must have an oversize label, issued by Intertek, stating the assembly is constructed in accordance with the certified design except for size. Acceptance of the oversize assembly is at the discretion of the Authority Having Jurisdiction.
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationFebruary 13, 2020
Certificate NumberWHI20 - 20797313
CriteriaASTM E84 (2013a)
CriteriaUL 1784 (2015)
CriteriaUL 10(d) (2014)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CriteriaCAN / ULC S102 (2018)
CSI Code08 30 00 Specialty Doors and Frames
CSI Code08 34 00 Special Function Doors
Listing SectionCATEGORY I - SMOKE & DRAFT CONTROL DOOR ASSEMBLIES