Intertek Directory of Building Products

Warm Springs 45-90 Minute Flush Doors Company: Warm Springs Composite Products

Composite Core Type, Swinging Flush Design Fire Door for installation in single swing or standard pairs 45 to 90 Minute locations.

LIMITATIONS
The following limitations are subject to specific door construction requirements. Please refer to Manufacturing and Machining sections of this Listing.
Minimum overall door thickness: 1-11/16"
Mortised or cylindrical latches with up to a 5" backset
Mortised automatic flushbolts

Mortised or surface mounted rim type fire exit hardware
Surface mounted vertical rod fire exit hardware
Concealed Vertical Rod (CVR) hardware

Electrical wire raceways
Vision panels: max.
100 sq.in. (90 min.)
Vision panels: max. 616 sq.in. each lite, max 1232 sq.in (45 & 60 min.)
Louvers: max. 524 sq.in.

Temperature Rise - 250°F @ 30 minutes
Surface mounted closers

Wood surface veneer
Plastic laminate veneer 0.050" thick
Wood crossbanding 1/16" thick
Surface mounted or mortised door bottoms
Concealed closer track and arm (45-60 min. only)
Maximum Size of Openings
The maximum opening sizes are subject to specific door construction requirements. Please refer to the Manufacturing section of this Listing.
CORE TYPE SWING MAXIMUM SIZE
Thermal-Lite Single 4'0" wide x 8'0" high
3'0" wide x 8'0" high* 
Pairs 6'0" wide x 7'0" high**
7'0" wide x 8'0" high***
MDS Mineral Core Single 4'0" wide x 9'0" high
Pairs 8'0" wide x 9'0" high****
AHI Single 4'0" wide x 9'0" high
Pairs 8'0" wide x 9'0" high****
G-P Gypsum Single 4'0" wide x 8'0" high
Pairs 8'0" wide x 8'0" high
WSCP-412 Single 4'0" wide x 9'0" high
Pairs 8'0" wide x 8'0" high*
*Additional requirements as noted in Manufacturing section
**3-point latching and 5" Tectonite meeting stile required
***4-point latching and 2" Tectonite stiles required
****4-point latching and 5" Tectonite stiles required for pairs over 8 ft. in height.

Evaluated to the following...
Positive Pressure - Category A
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing.

All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UL 10C".
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationMarch 27, 2020
Certificate NumberWHI20 - 20830611
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance45 Min Neutral Pressure
Fire Resistance60 Min PP Category A Door
Fire Resistance90 Min Neutral Pressure
Fire Resistance90 Min PP Category A Door
Fire Resistance45 Min PP Category A Door
Fire Resistance60 Min Neutral Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID30393
SwingSingle Swing
SwingStandard Pairs
Temperature Rise@ 30 Min = 250° F MAX Where Lites Do Not Exceed 100 IN2
Design Documents
No Results
Public Documents
No Results