Trussbilt 20-180 Min Vertically Stiffened Fire Doors Company: Trussbilt, LLC

Hollow Metal and Vertically Stiffened Doors (Swinging) (18, 16, 14 gauge) for installation in 20 minute up to and including 3 hour locations.
 
Thickness: 1-3/4" to 2"
Maximum Size of Openings: Single Swing - 48" wide x 120" high
Standard Pairs - 96" wide x 120" high (individual leaf: 48" wide x 120" high
Double Egress Pairs - 96" wide x 120" high (individual leaf: 48" wide x 120" high

Heavy Gauge Door Assemblies  (10, 12, 14 gauge) for installation in 20 minute up to and including 3 hour locations.
 
Thickness: 1-7/8" to 2-1/16"
Maximum Size of Openings: Single Swing - 48" wide x 96" high
Pairs - 96" wide x 96" high

**Pairs require 3pt or 4pt latching Surface bolts only.
Vision Panels
Ratings
Max. Area
Max. Width
Max. Height
3 Hour 100 in2 12" 33"
1 & 1-1/2 Hour 100 in2 12" 33"
1 & 1-1/2 Hour 552 in2 . 12" 46"
20 & 45 Minute 1296 in2 36" 54"
20 & 45 Minute 2856 in2 34" 84"
20 Minute w/o Hose 3289 in2 35-3/4" 92"
Maximum of 4 vision panels with 552 sq.in. for each panel.
Louvers

A maximum area of 516 sq.in. with a maximum width of 24" and a maximum height of 24". Cannot be used with vision panels. Cannot be used in doors rated 3 hours. Cannot be used in doors with Fire Exit Hardware.
Astragals
Required on 3 hour rated pairs or double egress. Required on 1-1/2 hour and less rated doors taller than 96".
Hardware
Active Leaf: Single Point or Fire Exit Hardware; Inactive Leaf: Top and Bottom Bolts; Concealed or Surface Mounted Vertical Rod Fire Exit Hardware; Open Back Strikes or Electric Strikes Used in Conjunction with Listed Fire Exit Hardware on Opposing Leaf (Power Supply to Electric Strike is by way of Electric Hinge) (Listed Surface Mounted or Concealed Vertical Rod Fire Exit Hardware or Self-Latching or Automatic Flush Bolts are required with Open Back Strike); Listed Latchsets; Hinges per NFPA-80.
Vision Panels
 
Ratings
Max. Area
Max. Width
Max. Height
3 Hour 100 in2 12" 33"
1 & 1-1/2 Hour 100 in2 12" 33"
1 & 1-1/2 Hour 552 in2 . 12" 46"
20 & 45 Minute 1296 in2 36" 54"
20 & 45 Minute 2856 in2 34" 84"
20 Minute w/o Hose 3289 in2 35-3/4" 92"
Maximum of 4 vision panels with 552 sq.in. for each panel.
Louvers
A maximum area of 516 sq.in. with a maximum width of 24" and a maximum height of 24". Cannot be used with vision panels. Cannot be used in doors rated 3 hours. Cannot be used in doors with Fire Exit Hardware.
Hardware
Listed Latchsets; Hinges per NFPA-80; Food Pass Through; Sliding Track (Airteq Model 8250 Door Operator).
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)
Listing Report Return to Search
Attributes
CriteriaUL 10(b) 2008 (R2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire ResistanceNeutral Pressure
Fire Resistance60 Min Neutral Pressure
Fire Resistance20 Min Neutral Pressure
Listing SectionDOORS