Pressed Steel Door Frame (16 gauge) (Knock-Down) for installation in 3 hour locations in steel/wood stud drywall or masonry openings, including double egress.
| Maximum Size of Openings: |
8'4-3/8" wide x 10'0" high |
| Maximum Overall Dimensions: |
105" wide x 124" high |
| Minimum Throat Opening: |
3-1/2" (2" with 20 minute rating) |
Pressed Steel Door Frame (Double Egress) (12, 14, or 16 gauge) (Welded Up) for installation in 1-1/2 hour locations in steelwood stud drywall or masonry openings.
| Maximum Size of Openings: |
8'4-3/8" wide x 9'0" high |
| Maximum Overall Dimensions: |
104-3/8" wide x 110" high |
| Minimum Throat Opening: |
3-1/2" |
Pressed Steel Side Light Door Frame (14, 16 gauge) (Welded Up) for installation in 1 hour locations in steel/wood stud drywall or masonry openings.
Limitations: "Firelight" listed glazing (or equivalent) must be used, and prior approval must be obtained from the authority having jurisdiction, as applicable code requirements may vary. All listing conditions for the glazing must be satisfied.
| Maximum Overall Dimensions: |
10'2" wide x 10'1" high |
| Minimum Wall Thickness: |
4-7/8" |
| Maximum Clear View Glazing Area: |
2.721 sq.in. |
| Stop Height: |
5/8" |
Pressed Steel Side Light Door Frame (16 gauge)(Welded Sections or Fully Welded or KD) for installation in 45 minute locations in steel/wood stud drywall or masonry openings.
Limitations: Side Lights require Pemko FG 3000 Compound and Pilkington Glass. Prior approval must be obtained from the authority having jurisdiction, as applicable code requirements may vary. All the listing conditions for the glazing must be satisfied.
| Total Maximum Width: |
12'8" Drywall; 13'6" Masonry Wall |
| Total Maximum Height: |
11'4" Drywall; 12'0" Masonry Wall |
| Minimum Side Light Stop Height: |
5/8" |
| Minimum Throat Opening |
5-3/4" |
Pressed Steel Door Frame "FR100" (12, 14, or 16 gauge) (Welded) for installation in 1-1/2 hour locations in steel/wood stud drywall or masonry openings, including double egress.
| Singles: |
4'0" wide x 8'0" high |
| Standard Pairs (including Double Egress): |
8'0" wide x 8'0" high |
| Minimum Throat Opening: |
4" |
Pressed Steel Door Frame "FR200" (Double Egress) (12, 14, or 16 gauge) for installation in 1-1/2 hour locations in steelwood stud drywall or masonry openings.
| Singles: |
4'0" wide x 8'0" high |
| Standard Pairs (including Double Egress): |
8'0" wide x 8'0" high |
| Minimum Wall Thickness: |
4" |
*NOTE: Door height of 10'0" is allowed with 18 gauge buck.