Titan Metal 90 Min Steel Fire Door Frame Adjustable Throat, Split (Fully Welded)
Company: Titan Metal Products, Inc.
DOOR FRAMES
Pressed Steel Door Frame (16 gauge) (Welded Up) (Fixed Sections or Adjustable Split Sections) for installation in 1-1/2 hour locations in steel/wood stud drywall opening where permitted by the Authority Having Jurisdiction.
Maximum Size of Door Openings: |
8'0" wide x 9'0" high |
Maximum Overall Dimensions: |
104" wide x 112" high |
Minimum Wall Thickness and Throat Opening: |
3" |
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been tested to the following standards:
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies;
NFPA-252, Standard Methods of Fire Tests of Door Assemblies;
UBC-7-2-94, Uniform Building Code;
UL-10(b), Fire Tests of Door Assemblies;
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All frames are identified by either a label or embossed marking bearing the wording "Listed (Product)" and the WHI Certification Mark. Frames rated for less than 3 hours also bear the time interval. Frame labels that do not include a time interval are rated for 3 hours.
CATEGORY C - PROPRIETARY FRAMES
Pressed Steel Door Frame (16 gauge) (Welded-Up) (Fixed Sections, Adjustable Split Sections) for installation in 90 minute locations in Steel/Wood Stud Drywall Opening where permitted by the authority having jurisdiction.
Max. Size of Door Openings: |
8'0" wide x 9'0" high |
Max. Overall Dimensions: |
104" wide x 112" high |
Min. Wall Thickness and Throat Opening: |
3" |
Evaluated to the following:
This category includes frames not based on UL-63 construction Type (such as aluminum, wood, light gauge steel, composite, etc.). These listings will reference specific door types for which each frame is qualified. All frames listed in this section may be used in positive pressure assemblies per the terms and limitations of the individual listing.
All frames in this category are identified by a label or marking bearing the wording, "Listed Fire Door Frame", the Warnock Hersey Certification Mark, "UBC-7-2-97/UL-10C. Frames rated at less than 3 hours will have a time interval noted on the label/marking. See Positive Pressure Section Header for more information.