Hollow Metal Type (16, 18 gauge) (Steel-Faced) (Insulated) (Acoustical), Swinging Flush Design Fire Door for installation singly in 1-1/2 hour locations.
Limitations: Unit, Mortise or Cylindrical Latches/Mortised or Surface Mounted Vertical Rod Fire Exit Hardware/Lights - 100 sq.in. using Firelite Glazing/Mortised or Surface Mounted Top and Bottom Bolts/Mortised or Surface Mounted Drop Seals/Temp. Rise - 250°F @ 30 minutes
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
|
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)