Hollow Metal Type (16 gauge), Swinging Flush Design Fire Door for installation singly or in pairs (including Double Egress) in 20 minute to 3 hour locations.
Limitations: Cylindrical Latches/Mortised Top and Bottom Bolts/Temp. Rise 250°F @ 30 minutes/Ball bearing Hinges permitted. Stainless steel, brass, or aluminum cladding - (aluminum and brass cladding not permitted on meeting edges of pairs).
Maximum Size of Openings: |
1-1/2 hr. Singles - 4'6" wide x 10'0" high
3 hr. Singles - 4'0" wide x 8'0" high
1-1/2 hr. Standard Pairs - 8'0" wide x 10'0" high
3 hr. Standard Pairs - 8'0" wide x 8'0" high
1-1/2 hr. Double Egress Pairs - 8'0" wide x 10'0" high |
Note: Doors - 10'0"
Hollow Metal Type (16, 18 gauge) (Steel-Faced) (Vertically-Stiffened) (Insulated), Swinging Flush Design Dutch Doors for installation in single swing 20 minute to 3 hour locations.
Limitations: Mortise or Cylindrical Latches/Minimum Bolt Throw - 3/4"/Minimum Backset - 5", Mounted on the Bottom Leaf, Latching into the Door Frame or Top Leaf. OR Mortise or Cylindrical Latches/Minimum Bolt Throw - 3/4"/Maximum Backset - 5"/Mounted on the Top Leaf/Latching into the Bottom Leaf or Door Frame. OR Flat Bar Astragal/2" wide x 1/8" thick x length ( = door width) must be used on the Top Leaf at the Meeting Edge. Stainless steel or aluminum cladding applied to surface of the door face only.
Maximum Size of Openings: |
4'0" wide x 8'0" high |
Fire Resistive Glass allowed up to the maximum size tested per glazing and vision kit manufacturers listings. Glass must be listed for fire door applications (UL 10B, UL10C, NFPA 252, and/or CAN/ULC S104) in the sizes specified. Vision kit must be listed for use with this type of glass and up to the sizes specified.
Fire Protective Glass in 20 - 45 minute doors allowed per glazing and vision kit manufacturers listings.
Fire Protective Glass in 60 - 180 Minute Doors: 100in
2
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies
UL-10(c), Standard for Positive Pressure Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)
The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.