Intertek Directory of Building Products

ABS Encore 20 Min (with hose) Routed Simulated Panel Fire Door PP Company: American Building Supply, Inc.

Wood Core Type (Particle Board Core) Routed Simulated Panel, Swing-Type Fire Door for installation singly or in pairs with 4-point latching in 20 minute locations (with hose). For use in any "Category C - Standard" Frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions. Field-Applied Edge Seal System is required. Refer to the door manufacturer's installation instructions for Edge-Seal System requirements.
 
Limitations: Cylindrical and Mortise Latches with Maximum 2-3/4" Backset and Minimum 1/2" Bolt Throw for single swing door, Rim or Mortise Type Fire Exit Hardware/Automatic or Manual Flush Bolts/Surface Bolts/Surface-Mounted Closer/Concealed Overhead Closer/EPT/Door Pairs with Hose Stream require 4-Point Latching.
 
Configuration Maximum Size*
Single 4' 0" wide x 8' 0 " high
Pair** 8'0" wide x 8'0" high
Double Egress NA
 
*See manufacturer's installation instructions for additional information, restrictions and limitations.
Testing Standards: UBC-7-2-97/UL-10C (Positive Pressure).
 
**Doors in pairs require minimum 4-point latching. 
 
Evaluated to the following...
 
This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.
 
These assemblies are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
 
All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
 
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL 10C". 
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance20 Min w/Hose Positive Pressure
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID31527
SwingSingle Swing
SwingStandard Pairs
Design Documents
No Results
Public Documents
No Results