Intertek Directory of Building Products

American Openings 20 Min Milan Wood Fire Door Company: American Openings

PRODUCT COVERED
 
American Openings 20 Min Milan Wood Fire Door
 
PRODUCT DESCRIPTION
 
Panel-type, stile and rail, wood fire door, for installation singly in 20 minute locations.  For use in any Category C – Standard Frame.  These doors may also be installed in frames listed in Category C – Proprietary Frames, in accordance with the frame manufacturer's individual listing.
 
Maximum Sizes:
Single-Swing 3'0" x 7'0"
 
Limitations:  Mortise lock, Cylindrical latches with minimum 1/2 in. bolt throw and up to 2-3/4 in. backset, cylindrical deadbolts, surface applied hardware, viewers,  surface plates up to 12 in. high, card reader, surface mount automatic door bottom.
 
 
CATEGORY B – FIRE DOORS
 
This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.
 
These assemblies are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
 
All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
 
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C".
 
 
Listing Report Return to Search
Attributes
CriteriaASTM E152-81a
CriteriaCSFM 43.7
CriteriaUBC 7-2 (1997)
CriteriaUBC 7-2 (1994)
CriteriaCAN / ULC S104 (1980) (R1985)
CriteriaASTM E2074 (2004)
CriteriaNFPA 252 (2012)
CriteriaUL 10(b) (2008)
CriteriaNFPA 252 (2008)
CriteriaUL 10(c) (1998) (R2001)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance20 Min w/Hose Negative Pressure
Fire Resistance20 Min w/Hose Positive Pressure
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Listing SectionDOORS
Spec ID31531
SwingSingle Swing
Design Documents
No Results
Public Documents
No Results