Pottorff Co. Ceiling Dampers Company: Pottorff


Ceiling Damper for Horizontal Installation in Air Duct Outlets of Restrained or Unrestrained Floor-Ceiling and Roof-Ceiling Assemblies with Fire Rating up to 3-Hours.
 
Model Nos.
Shape
Max. Area (sq.in)
Max. Width
Max. Len.
Max. Dia.
Min. Width
Min. Len.
Min. Dia.
CFD-15
CFD-15ES
CFD-15LP
CFD-15PLES
Square or Rectangular
576
24"
24"
NA 5" 5" NA
CFD-15SB
CFD-15SBES
Square or Rectangular
288
24"
12"
NA 5" 5" NA
CFD-15R
CFD-15RES
Round
452
NA
NA
24" NA NA 5"
CFD-20
CFD-20ES
Square or Rectangular
576
24"
24"
NA 5" 5" NA
CFD-521* Square or Rectangular
324 (18" x 18")
or 144 (24" x 6")
18"
24"
NA 6" 6" NA
RD1** Square
156.25"
12-1/2"
12-1/2"
NA
12-1/2"
12-1/2"
NA
RD2** Rectangular
268.65"
12-1/2"
21-1/2"
NA
12-1/2"
21-1/2"
NA
RD3** Rectangular
396"
18"
22"
NA
18"
22"
NA
RD4** Rectangular
80"
10"
7-15/16"
NA
10"
7-15/16"
NA

†CFD-15 Models can be installed with 1- x 1/2-in. x 20 GA mounting angle or boot rails. 

*CFD-521 can only be installed in UL Design No. L521, L546, L550 & P522 Floor/Ceiling and Roof/Ceiling Assemblies.

**Listing for dampers only, and damper may be used with UL-listed exhaust fans manufactured by Broan.

Note:
  • 1. All dimensions have a tolerance of ± 1/16".
    2. The fire rating of the floor/ceiling or roof/ceiling assembly (in which a given damper is installed) determines the overall fire rating. Thus, a 3-hour fire rated damper installed in a 1-hour fire rated (wood truss type, combustible floor/ceiling) assembly results in an overall fire rating of 1-hour for the whole unit.
    3. The total number of damper shall not exceed the total number of 12" diameter or larger duct openings in any individual floor/ceiling or roof/ceiling design.
    4. The installation must be per manufacturer's installation instructions or NFPA-90A.
    5. Abbreviations: CFD = Ceiling Fire Damper; ES = Extended Sleeve; NS = No Sleeve; R = Round; LP = Low Profile; SB = Single Blade; ESC2 = Extended Sleeve with Side Collar; SC2 = Side Collar; ESR = Extended Sleeve with Round Collar Duct Connection; EST = Extended Sleeve Tapered; STC 2 = Extended Sleeve Tapered with Side Collar; NSB = No Sleeve with "B" type duct connection; ESET = Extended Sleeve with Extra Transion.

Sub-Manufacturer
C & S Air Products
5101 Blue Mound Road
Fort Worth, TX 76106

Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL-555, Fire Dampers & Ceiling Dampers
CAN/ULC-S112, Standard Method of Fire Test of Fire Damper Assemblies;
and are installed in accordance with the following:
NFPA-90A, Installation of Air Conditioning & Ventilating Systems.

Manufacturer's Instructions.
All assemblies are identified by all label bearing the wording, "Listed (Product)", a time interval, a serial number and the Warnock Hersey Certification Mark.
Listing Report Return to Search
Attributes
CriteriaASTM E119 (2005a)
CriteriaCAN / ULC S101 (2007)
CriteriaASTM E119 (2010)
CriteriaCAN / ULC S101 (2014)
CriteriaASTM E119 (2020)
CSI Code23 00 00 Heating, Ventilating, and Air Conditioning (HVAC)
CSI Code23 33 00 Air Duct Accessories
Fire Resistance3 Hour Fire Rated
Listing SectionDAMPERS
Spec ID31550