Pottorff Co. Ceiling Dampers
Company: Pottorff
Ceiling Damper for Horizontal Installation in Air Duct Outlets of Restrained or Unrestrained Floor-Ceiling and Roof-Ceiling Assemblies with Fire Rating up to 3-Hours.
|
Model Nos.
|
Shape
|
Max. Area (sq.in)
|
Max. Width
|
Max. Len.
|
Max. Dia.
|
Min. Width
|
Min. Len.
|
Min. Dia.
|
CFD-15†
CFD-15ES†
CFD-15LP†
CFD-15PLES† |
Square or Rectangular |
576
|
24"
|
24"
|
NA |
5" |
5" |
NA |
CFD-15SB
CFD-15SBES |
Square or Rectangular |
288
|
24"
|
12"
|
NA |
5" |
5" |
NA |
CFD-15R
CFD-15RES |
Round |
452
|
NA
|
NA
|
24" |
NA |
NA |
5" |
CFD-20
CFD-20ES |
Square or Rectangular |
576
|
24"
|
24"
|
NA |
5" |
5" |
NA |
| CFD-521* |
Square or Rectangular |
324 (18" x 18")
or 144 (24" x 6")
|
18"
|
24"
|
NA |
6" |
6" |
NA |
| RD1** |
Square |
156.25"
|
12-1/2"
|
12-1/2"
|
NA |
12-1/2"
|
12-1/2"
|
NA |
| RD2** |
Rectangular |
268.65"
|
12-1/2"
|
21-1/2"
|
NA |
12-1/2"
|
21-1/2"
|
NA |
| RD3** |
Rectangular |
396"
|
18"
|
22"
|
NA |
18"
|
22"
|
NA |
| RD4** |
Rectangular |
80"
|
10"
|
7-15/16"
|
NA
|
10"
|
7-15/16"
|
NA
|
†CFD-15 Models can be installed with 1- x 1/2-in. x 20 GA mounting angle or boot rails.
*CFD-521 can only be installed in UL Design No. L521, L546, L550 & P522 Floor/Ceiling and Roof/Ceiling Assemblies.
**Listing for dampers only, and damper may be used with UL-listed exhaust fans manufactured by Broan.
Note:
- 1. All dimensions have a tolerance of ± 1/16".
2. The fire rating of the floor/ceiling or roof/ceiling assembly (in which a given damper is installed) determines the overall fire rating. Thus, a 3-hour fire rated damper installed in a 1-hour fire rated (wood truss type, combustible floor/ceiling) assembly results in an overall fire rating of 1-hour for the whole unit.
3. The total number of damper shall not exceed the total number of 12" diameter or larger duct openings in any individual floor/ceiling or roof/ceiling design.
4. The installation must be per manufacturer's installation instructions or NFPA-90A.
5. Abbreviations: CFD = Ceiling Fire Damper; ES = Extended Sleeve; NS = No Sleeve; R = Round; LP = Low Profile; SB = Single Blade; ESC2 = Extended Sleeve with Side Collar; SC2 = Side Collar; ESR = Extended Sleeve with Round Collar Duct Connection; EST = Extended Sleeve Tapered; STC 2 = Extended Sleeve Tapered with Side Collar; NSB = No Sleeve with "B" type duct connection; ESET = Extended Sleeve with Extra Transion.
Sub-Manufacturer
C & S Air Products
5101 Blue Mound Road
Fort Worth, TX 76106
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL-555, Fire Dampers & Ceiling Dampers
CAN/ULC-S112, Standard Method of Fire Test of Fire Damper Assemblies;
and are installed in accordance with the following:
NFPA-90A, Installation of Air Conditioning & Ventilating Systems.
Manufacturer's Instructions.
All assemblies are identified by all label bearing the wording, "Listed (Product)", a time interval, a serial number and the Warnock Hersey Certification Mark.