Intertek Directory of Building Products

Coopers Fire Ltd. 20 Minute to 3 Hour Fire Rated FireMaster & SmokeStop Smoke and Fire Barrier (With Overlap) Company: Coopers Fire Ltd.

Coopers Fire Ltd. 3 Hour FireMaster & SmokeStop Smoke and Fire Barrier (With Overlap) protective curtain assembly, for use in steel stud/gypsum or masonry wall applications.

FIRE RATINGS
Test Standard Rating
UL 10D 180 minutes
UL 10B, UL 10C, NFPA 252 20 minutes without hose stream*
*Please note that acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.

AIR LEAKAGE RATINGS
Test Standard Test Type Ratinga, b
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
aThis assembly was tested with an artificial bottom seal. The assembly is not to be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) or for hoistway opening protection and lobby doorways where prohibited in Chapter 30 of the 2018 IBC
bA pair of two-inch brushes are required at the head of the curtain to meet air leakage ratings, a single one-inch brush at each side guide is optional based on test results.  Brushes must be listed & labeled for fire applications.

MAXIMUM SIZE LIMITATIONS
Certification Procedure Maximum Area Maximum Width Maximum Height
LABEL 93.5 sq ft 9’8” 9’8”
CERTIFICATE/LABEL  unlimited* unlimited* unlimited*
*Assemblies exceeding these dimensions must have an oversized label, issued by Intertek, stating the assembly is constructed in accordance with the certified design except for size. Acceptance of the oversize assembly is at the discretion of the Authority Having Jurisdiction.

MINIMUM SIZE LIMITATIONS (UL 1784 ONLY)*
Width Height
7' 0" 7' 0"
*Fire-only assemblies do not have a minimum size.

Minimum Bottom Bar weight: 0.30 lbs per sq. ft. of curtain area
Maximum Curtain Rivet spacing: 15” (380mm) on-center
Side Guide anchorage: 1/4" anchors spaced maximum 18” (455mm) on-center
Top Hood/Assembly mounting: maximum 40” (1000mm) on-center

Minimum overlap: 23-5/8" (600mm)
Passage Door (Optional): A passage door using a split bottom bar secured by stainless steel hook & loop may be incorporated into the curtain at overlap locations

 
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationAugust 04, 2023
Certificate NumberWHI23-11025807
CriteriaUL 1784 (2004)
CriteriaNFPA 252 (2008)
CriteriaUL 10(c) (2009)
CriteriaUL 10(b) (2008) (R2009)
CriteriaUL 10(d) (2009)
CriteriaNFPA 252 (2012)
CriteriaUL 1784 (2015)
CriteriaUL 10(d) (2014)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CSI Code08 30 00 Specialty Doors and Frames
Fire Resistance20 Min w/out Hose Negative Pressure
Fire Resistance20 Min w/out Hose Positive Pressure
Fire Resistance3 Hour Positive Pressure
Listing SectionSMOKE CONTROL DOOR ASSEMBLIES
Spec ID32660
Design Documents
No Results
Public Documents
No Results