Intertek Directory of Building Products

Steelcraft Steel Covered Hollow Metal (T Series*) Fire Door Company: Steelcraft Manufacturing / Schlage Lock Company LLC

Steel Covered Hollow Metal Type (14, 16, 18, 20 gauge) (Mineral Fiberboard Core Filled) ('T' Series*), Swinging Flush Design Fire Door for installation singly or in pairs in up to 3 hour locations. 1-3/4 door thickness.
In addition to the "T" Series door description, embossed panel doors may be signified by "CE", "CE" series with temperature rise cores are signified by "TE", "T" series door with square edge are signified by "ST", "T" series door for storm-resistant applications may be identified as "TH" series. 

Limitations:
Active Leaf - Single Point Latch or Fire Exit Hardware.
Inactive Leaf - Surface or Mortised Top and Bottom Bolts/Surface Mounted Vertical Rod Fire Exit Hardware.
Astragal required for all fire ratings (pairs), except standard swing pairs with vertical rod fire exit hardware in each leaf (1-1/2 hour maximum).
Louvers are not permitted.
100 sq.in of glass permitted (1-1/2 hour maximum).
Temp. Rise - 250°F for the first 30 minutes (450°F for vertical rod fire exit hardware & integral fire exit hardware). 

 
Maximum Size of Openings/Fire Ratings:
Singles
(14, 16,18 gauge)
4'0" x 9'0"
Pairs & DE
(14, 16,18 gauge)
8'0" x 9'0"
Singles
(20 gauge)
4'0" x 8'0"
 
Pair
(20 gauge)
8'0" x 8'0"
¾, 1 hr, 1-1/2 hr and 3 hour rating ¾, 1 hr, 1-1/2 hr and 3 hour rating ¾, 1 hr, 1-1/2 hr and 3 hour rating ¾, 1 hr, 1-1/2 hr and 3 hour rating
 
Maximum Size of Openings/Fire Ratings
Configuration: Hardware: Size/Rating:
Singles (1-3/4")
14, 16 & 18 gauge
Single Point Lock 4'0" x 9'0"
3 hour Maximum
Pair (1-3/4")
14, 16 & 18 gauge
Three Point Latch
with astragal
(single point on active,
top & bottom on inactive)
8'0" x 9'0"
3 hour Maximum
Singles (1-3/4")
20 gauge
Single Point Lock 4'0" x 8'0"
3 hour Maximum
Pair (1-3/4")
20 gauge
Three Point Latch
with astragal
(single point on active,
top & bottom on inactive)
8'0" x 8'0"
3 hour Maximum
Singles (1-3/4")
14, 16 & 18 gauge
Fire Exit Hardware 4'0" x 9'0"
3 hour Maximum
Pair (1-3/4")
14, 16 & 18 gauge
Mortise Fire exit on active, Vertical rod (SVR or CVR) Fire exit on inactive door with closed back strike and astragal 8'0" x 9'0"
3 hour Maximum
Pair (1-3/4")
14, 16 & 18 gauge
 Two Vertical rod exit devices (SVR or CVR) without astragal 8'0" x 9'0"
1-1/2 hour Maximum
Double Egress
 (1-3/4")
14, 16 & 18 gauge
Vertical rod exit device (SVR or CVR) with astragal 8'0" x 9'0"
3 hour Maximum
Singles (1-3/4")
20 gauge
Fire Exit Hardware 4'0" x 8'0"
3 hour Maximum
Pair (1-3/4")
20 gauge
Mortise Fire exit on active, Vertical rod (SVR or CVR) Fire exit on inactive door with closed back strike and astragal 8'0" x 8'0"
3 hour Maximum
 
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies
UL-10(c), Positive Pressure Tests of Fire Doors
UL-1784
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark. (Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationNovember 15, 2019
Certificate NumberWHI19-20392302
CriteriaCAN4 S104 (1985)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaUL 10(c) (2009) (R2015)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance20 Min w/Hose Positive Pressure
Fire Resistance45 Min Positive Pressure
Fire Resistance90 Min Positive Pressure
Fire Resistance60 Min Positive Pressure
Fire Resistance3 Hour Positive Pressure
Listing SectionDOORS
Spec ID32717
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents
No Results