Intertek Directory of Building Products

Steelcraft Falcon Series Swinger and Steel Stiffened 20-180 Min Hollow Metal Fire Doors Company: Steelcraft Manufacturing / Schlage Lock Company LLC

Falcon Series Doors

 

Hollow Metal Type (18, 20 gauge) (Mineral Fiberboard Core Filled) Swinging Flush Design Fire Doors for installation singly or in pairs in 3-hour locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Temp. Rise - 250°F @ 30 minutes/Pairs Astragal/Lights - up to 100 sq.in. (when permitted by AHJ using special glazing).

Maximum Size of Openings

Singles - 4'0" wide x 7'2" high.

Pairs - 8'0" wide x 7'2" high 

 

Hollow Metal Type (16, 18 gauge) (Vertically-Stiffened Mineral Fiber Insulation) Swinging Flush Design Fire Doors for installation singly or in pairs in 3-hour locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Pairs Astragal/Lights - up to 100 sq.in. (when permitted by AHJ using special glazing).

Maximum Size of Openings

Singles - 3'6" wide x 7'2" high.

 

Pairs - 7'0" wide x 7'2" high 

 

Hollow Metal Type (16, 18, 20 gauge) (Foam-Filled), Swinging Flush Design Fire Doors for installation singly or in pairs in 3-hour locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Pairs Astragal/Lights - up to 100 sq.in. (when permitted by AHJ using special glazing).

Maximum Size of Openings

Singles - 4'0" wide x 8'0" high.

 

Pairs - 8'0" wide x 8'0" high 

 

Hollow Metal Type (16, 18, 20 gauge) (Paper Honeycomb Filled), Swinging Flush Design Fire Doors for installation singly or in pairs in 3-hour locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Pairs Astragal/Lights - up to 100 sq.in. (when permitted by AHJ using special glazing).

Maximum Size of Openings

Singles - 4'0" wide x 8'0" high.

 

Pairs - 8'0" wide x 8'0" high 

 

Hollow Metal Type (18, 20 gauge) (Mineral Fiberboard Core Filled) Swinging Flush Design Fire Doors for installation singly or in pairs in 90 and 45 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Temp. Rise - 250°F @ 30 minutes/Lights - up to 100 sq.in.

Maximum Size of Openings

Singles - 4'0" wide x 7'2" high.

 

Pairs - 8'0" wide x 7'2" high 

 

Hollow Metal Type (16, 18 gauge) (Vertically-Stiffened, Mineral Fiber Insulation) Swinging Flush Design Fire Doors for installation singly or in pairs in 90 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Louvers 24" x 24"/Lights - up to 100 sq.in.

Maximum Size of Openings

Singles - 3'6" wide x 7'2" high.

 

Pairs - 7'0" wide x 7'2" high 

 

Hollow Metal Type (16, 18, 20 gauge) (Foam-Filled), Swinging Flush Design Fire Doors for installation singly or in pairs in 90 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Pairs Astragal/Lights - up to 100 sq.in.

Maximum Size of Openings

Singles - 4'0" wide x 8'0" high.

 

Pairs - 8'0" wide x 8'0" high 

 

Hollow Metal Type (16, 18, 20 gauge) (Paper Honeycomb Filled), Swinging Flush Design Fire Doors for installation singly or in pairs, including double egress, in 90 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Louvers - 24" x 24"/Lights - up to 100 sq.in.

Maximum Size of Openings

Singles - 4'0" wide x 8'0" high.

Pairs - 8'0" wide x 8'0" high 

 

Double Egress - 8'0" wide x 8'0" high

 

Hollow Metal Type (16, 18 gauge) (Vertically-Stiffened, Mineral Fiber Insulation) Swinging Flush Design Fire Doors for installation singly or in pairs in 90 and 20 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Louvers - 24" x 24" (not permitted in 20 minute)/Lights - up to 1,296 sq.in.

Maximum Size of Openings

Singles - 3'6" wide x 7'2" high.

 

Pairs - 7'0" wide x 7'2" high 

 

Hollow Metal Type (16, 18, 20 gauge) (Foam-Filled), Swinging Flush Design Fire Doors for installation singly or in pairs in 45 and 20 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Louvers - 24" x 24" (not permitted in 20 minute)/Lights - up to 1,296 sq.in.

Maximum Size of Openings

Singles - 4'0" wide x 8'0" high.

 

Pairs - 8'0" wide x 8'0" high 

 

Hollow Metal Type (16, 18, 20 gauge) (Paper Honeycomb-Filled), Swinging Flush Design Fire Doors for installation singly or in pairs in 45 and 20 minute locations.

Limitations

Unit, Mortise or Cylindrical Latches with up to a 5" Backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts/Louvers - 24" x 24" (not permitted in 20 minute)/Lights - up to 1,296 sq.in.

Maximum Size of Openings

Singles - 4'0" wide x 8'0" high.

 

Pairs - 8'0" wide x 8'0" high 

 

Double Egress - 8'0" wide x 8'0" high

Listing for Multiple Listee. Agreement for Multiple Listing kept in client documents.

 

 

 

 

 

 

 

Listing Report Return to Search
Attributes
CriteriaNFPA 80 (1999)
CriteriaNFPA 252 (1995)
CriteriaASTM E152-81a
CriteriaUL 10(c) (1998)
CriteriaCSFM 43.7
CriteriaCAN4 S104 (1985)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaNFPA 252 (2012)
CSI Code08 11 00 Metal Doors and Frames
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire Resistance20 Min w/Hose Stream NP
Listing SectionDOORS
Spec ID32718
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents
No Results