Intertek Directory of Building Products

Steelcraft Covered Hollow Metal (B Series) Vertically Steel-Stiffened Fire Doors Company: Steelcraft Manufacturing / Schlage Lock Company LLC

Steel Covered Hollow Metal Type (18, 16, 14 gauge) (Vertically Steel-Stiffened), (Mineral Wool Filled, or Kraft Honeycomb Filled, or Polystyrene Foam Filled). ('B' Series*), Swinging Flush Design Fire Door for installation singly or in pairs in up to 3 hour locations.

*Doors manufactured as ''B' series for storm-resistant applications may be identified as PW series.


Limitations:

Active Leaf - Single Point Latch or Fire Exit Hardware.
Inactive Leaf - Surface or Mortised Top and Bottom Bolts/Surface Mounted or Concealed Vertical Rod Fire Exit Hardware. 16 & 18 gage door pairs can incorporate an Open Back Strike on one leaf used in conjunction with a listed single point latch or fire exit hardware on the opposing leaf. Listed surface mounted or concealed vertical rod fire exit hardware, or self-latching or automatic flush bolts, are required on leaf in which the open-back strike is mounted.
Astragal required on 3-hour pairs, optional on 1-1/2 hour pairs.
Louvers - 24" x 30" maximum, but not permitted on doors with glass lights.

When each leaf of a standard swing pair is equipped with listed concealed or surface mounted vertical rod fire exit hardware,the maximum rating shall be 1-1/2 hours, and the astragal shall be omitted.  Double egress pairs for a maximum or 1-1/2 hours may have the astragal omitted.

MAXIMUM SIZES

 
Maximum Size of Openings/Fire Ratings:
Singles (18, 16 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
4'0" wide x 10'0" high
3 Hour Maximum
Singles (14 gauge) (1-3/4") Single Point Lock or Fire Exit Hardware 4'0" wide x 8'0" high
3 Hour Maximum
Singles (14 gauge) (1-3/4") Single Point Lock or Fire Exit Hardware 4'0" wide x 10'0" high
1-1/2 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Single Point Lock or Fire Exit Hardware 8'0" wide x 8'0" high
3 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
8'0" wide x 10'0" high with astragal
1-1/2 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
8'0" wide x 8'0" high without astragal
1-1/2 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Two Vertical Rod Fire Exit Devices (SVR or CVR)  8'0" wide x 10'0" high without astragal
1-1/2 Hour Maximum
Pairs (18, 16 gauge) (1-3/4") Single Point Lock or Fire Exit Hardware With Open Back Strike Without Astragal 8'0" wide x 8'0" high
1-1/2 Hour Maximum
Double Egress Pairs
(18, 16 gauge) (1-3/4")
Fire Exit Hardware 8'0" wide x 10'0" high
3 Hour Maximum
Double Egress Pairs
(14 gauge) (1-3/4")
Fire Exit Hardware
 
8'0" wide x 8'0" high
3 Hour Maximum
Double Egress Pairs
(18, 16, 14 gauge) (1-3/4")
Fire Exit Hardware 8'0" wide x 10'0" high with astragal
1-1/2 Hour Maximum
Double Egress Pairs
(18, 16, 14 gauge) (1-3/4")
Fire Exit Hardware 8'0" wide x 8'0" high without astragal
3/4 - 1-1/2 Hour Maximum
Double Egress Pairs
(18, 16, 14 gauge) (1-3/4")
Fie Exit Hardware 8'0" wide x 10'0" high without astragal
20 Minute With or Without Hose Stream

 
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationNovember 15, 2019
Certificate NumberWHI19-20392303
CriteriaASTM E2074 (2000)
CriteriaCAN4 S104 (1985)
CriteriaASTM E152-81AE02
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance20 Min w/Hose Stream PP Cat A Door
Fire Resistance60 Min PP Category A Door
Fire Resistance3 Hour PP Category A Door
Fire Resistance90 Min PP Category A Door
Fire Resistance45 Min PP Category A Door
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID32719
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents
No Results