Intertek Directory of Building Products

Steelcraft 20-180 Minute "L" Series Hollow Metal Fire Doors Company: Steelcraft Manufacturing / Schlage Lock Company LLC

Steel Covered Hollow Metal Type (14, 16, 18, 20 gauge) (Paper Honeycomb or Combination Paper Honeycomb/Polystyrene Filled) ('L' Series*), Swinging Flush Design Fire Door for installation singly or in pairs including double egress in up to 3 hour locations.
*Embossed panel door designs may be called 'L' Series or 'CE' Series doors. Doors with square hinge and/or lock edges may be identified as 'SL' or 'SZ' Series. Doors manufactured as 'L' Series for storm resistant applications may be identified as 'H' Series. 'L' Series door construction is also used for 'RL' Series doors and may be identified as such. Dutch doors are fabricated in accordance with 'L' Series requirements.
Limitations:
Active Leaf - Single Point Latch or Fire Exit Hardware.
Inactive Leaf - Surface or Mortised Top and Bottom Bolts/Surface Mounted on Concealed Vertical Rod Fire Exit Hardware/14, 16, 18 gauge doors can incorporate an Open-Back Strike/Power supply to electric lock is by way of electric hinge or power transfer unit/Open-Back Strike on one leaf used in conjunction with a listed single point latch or fire exit hardware on the opposing leaf/Listed Surface Mounted or Concealed Vertical Rod Fire Exit Hardware or Self- Latching or Automatic Flush Bolts are required on leaf in which the open-back strike is mounted.
Astragal required on 3 hour pairs and is optional on 1-1/2 hour pairs.
Louvers - 24" x 30" maximum, but not permitted on doors with glass lights.
When each door leaf of a standard swing pair is equipped with listed concealed or surface mounted vertical rod fire exit hardware the maximum rating shall be 1-1/2 hours and the astragal shall be omitted. Double Egress pairs for a maximum of 1-1/2 hours may have the astragal omitted.
Dutch Design Doors are limited to a single swing with the use of a single point latch in both door leaves. Top Lock may latch into strike jamb or into the top of the bottom leaf.  As an alternate, a listed, self-latching flushbolt may be used in the bottom of the top leaf, to latch into the top of the bottom leaf. Astragal is required, 1/2 shelf is optional. Louvers are not permitted and glass light is limited to 100 sq.in.
 
Maximum Size of Openings/Fire Ratings:
Singles (20 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
3'8" wide x 7'2" high
3 Hour Maximum
Singles (20 gauge) (1-3/4") Single Point Lock 4'0" wide x 10'0" high
1-1/2 Hour Maximum
Singles (20 gauge) (1-3/4") Fire Exit Hardware 4'0" wide x 7'2" high
1-1/2 Hour Maximum
Singles (18, 16 gauge) (1-3/4") Single Point Lock 4'0" wide x 10'0" high
3 Hour Maximum
Singles (18, 16, 14 gauge) (1-3/4") Fire Exit Hardware 4'0" wide x 8'0" high
3 Hour Maximum
Singles (18, 16, 14 gauge) (1-3/4") Fire Exit Hardware 4'0" wide x 10'0" high
1-1/2 Hour Maximum
Singles (14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
4'0" wide x 8'0" high
3 Hour Maximum
Pairs (20 gauge) (1-3/4") Single Point Lock 8'0" wide x 7'2" high
1-1/2 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
8'0" wide x 10'0" high
1-1/2 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
8'0" wide x 8'0" high
3 Hour Maximum
Pairs (14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
8'0" wide x 8'0" high
3 Hour Maximum
Pairs (18, 16, 14 gauge) (1-3/4") Single Point Lock or
Fire Exit Hardware
with Open-Back Strike
8'0" wide x 7'2" high
1-1/2 Hour Maximum
Double Egress Pairs
(18, 16, 14 gauge) (1-3/4")
Fire Exit Hardware 8'0" wide x 7'2" high
3 Hour Maximum
Double Egress Pairs
(18, 16, 14 gauge) (1-3/4")
Fire Exit Hardware 8'0" wide x 9'0" high
1-1/2 Hour Maximum
Dutch Singles
(18, 16 gauge)
2 Single Point Locks 4'0" wide x 7'2" high
3 Hour Maximum
 
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
ASTM-2074-00, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies
UL-10(c), Positive Pressure Tests of Fire Doors
UL-1784
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark. (Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationNovember 15, 2019
Certificate NumberWHI19-20392306
CriteriaCAN4 S104 (1985)
CriteriaASTM E152-81AE02
CriteriaASTM E2074 (2004)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance20 Min w/Hose Stream PP Cat A Door
Fire Resistance60 Min PP Category A Door
Fire Resistance3 Hour PP Category A Door
Fire Resistance90 Min PP Category A Door
Fire Resistance45 Min PP Category A Door
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Smoke and Draft ControlSmoke Leakage < 3 cfm/sq ft per UL 1784
Spec ID32720
SwingSingle Swing
SwingStandard Pairs
SwingDutch
SwingDouble Egress