PRODUCT COVERED
Falcon Door SZ Series Fire Door
PRODUCT DESCRIPTION
Foam Filled Steel Fire Doors for installation Singly or in Pairs in 3 hour positive pressure assmblies, with temperature rise greater than 650°F at 30 minutes.
Limitations
Maximum Sizes
Single Swing
45 mm (1.75 inches) Minimum Thickness
1208 mm (48 inches) Maximum Width
2416 mm (96 inches) Maximum Height
Pairs
45 mm (1.75 inches) Minimum Thickness
2416 mm (96 inches) (each leaf: 1208 mm (48 inches)) Maximum Width
2416 mm (96 inches) Maximum Height
Vision Panels maximum 1296 sq. inches for 20 and 45 minute locations; 100 sq inches for 60 and 90 Minute locations. Glazing kit for light kits requires use of minimum 18 ga. Steel channel reinforcement attached to both faces around the vision panel cutout.
Evaluated to the following...
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL 10C".