Intertek Directory of Building Products

Smoke Guard® Model 2500 Company: Smoke Guard, Inc.

Product Covered:
Smoke Guard Model 2500 curtain assembly
Product Description:
The Smoke Guard M2500 systems consist of an ASTM E84 Listed flame and smoke resistance rated filament glass fabric (either SGTex-10a, -10b, -10c, -20, or -30) wound onto a tube containing an internal drive system.  Contained in a sheet metal housing, the curtain assembly is comprised of support rollers and associated electronics.  Sewn loops along the curtain edges are captured in vertical side guides during system deployment and the bottom edge of the curtain is attached to a weighted bottom bar.  If the system encounters an alarm, the releasing device activates deploying the curtain. In the event of main power failure, an integrated battery system maintains the system.  Should main and backup power systems fail, the curtain will deploy in a controlled manner under the influence of gravity (Gravity Fail Safe).  If required, wall switches are provided on each side of the curtain, allowing occupants to momentarily raise the curtain to egress.  After the alarm condition clears, the curtain automatically rewinds into the housing.
 
The Smoke Guard M2500 flame and smoke resistant system, utilizing the SGTex-30 fabric, is also recognized for use in fire-resistance rated construction (as tested in accordance with UL10B, UL10C, UL10D and NFPA 252 and as described below).
 
The following table pertains to the Smoke Guard M2500 system with SGTex-10a, -10b, -20, and -30 fabric curtains.  A representative sample of the product, having maximum width and height dimensions of 144” x 144”, was tested in accordance with the following Standards at Intertek:  UL1784
Test Method   Property Results
UL 1784 Max. air leakage at 0.3 in. of w.c. pressure differential @ ambient 96°F. <3 cfm/ft2
UL 1784 Max. air leakage at 0.3 in. of w.c. pressure differential @ 400°F. <3 cfm/ft2
2009 IBC Section 711.5.2 Criteria+ Where required elsewhere in the code, doors and smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784.  The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot (0.015424 m3/(s • m2)) of door opening at 0.10 inch (24.9 Pa) of water for both ambient temperature test and the elevated temperature exposure test.  Installation of smoke doors shall be in accordance with NFPA 105. Complies
2012 & 2015 IBC Section 710.5.2.2 Criteria+ Where required elsewhere in the code, doors and smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784.  The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot (0.015424 m3/(s • m2)) of door opening at 0.10 inch (24.9 Pa) of water for both ambient temperature test and the elevated temperature exposure test.  Installation of smoke doors shall be in accordance with NFPA 105. Complies
National Building Code of Canada 2015 Section 3.1.8.5(7) Complies
ASTM E84 Test for Surface Burning Characteristics of Building Materials FS<25
SD<450
+The Smoke Guard M2500 flame and smoke resistant system with either SGTex-10a, -20 or -30 fabric meets the 2009 IBC Section 711.5.2, and 2012 and 2015 IBC Sections 710.5.2.2 criteria when limited to a minimum curtain height of 2 feet with an unlimited width.  This determination presumes that the actual installations will include a bottom bar, gasketing and a flat level floor or sill that will provide an equivalent seal between the bottom bar and floor to that obtained in the referenced tests.
 
The following table pertains to the Smoke Guard M2500 system with SGTex-10c fabric curtain
Test Method   Property Results
UL 1784 Max. air leakage at 0.2 in. of w.c. pressure differential @ ambient 96°F. <3 cfm/ft2
UL 1784 Max. air leakage at 0.2 in. of w.c. pressure differential @ 400°F. <3 cfm/ft2
2009 IBC Section 711.5.2 Criteria+ Where required elsewhere in the code, doors and smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784.  The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot (0.015424 m3/(s • m2)) of door opening at 0.10 inch (24.9 Pa) of water for both ambient temperature test and the elevated temperature exposure test.  Installation of smoke doors shall be in accordance with NFPA 105. Complies
2012 & 2015 IBC Section 710.5.2.2 Criteria+ Where required elsewhere in the code, doors and smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784.  The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot (0.015424 m3/(s • m2)) of door opening at 0.10 inch (24.9 Pa) of water for both ambient temperature test and the elevated temperature exposure test.  Installation of smoke doors shall be in accordance with NFPA 105. Complies
National Building Code of Canada 2015 Section 3.1.8.5(7) Complies
ASTM E84 Test for Surface Burning Characteristics of Building Materials FS<25
SD<450
The following table pertains to the Smoke Guard M2500 system with SGTex-30 fabric curtain only.  A representative sample of the product, having maximum width and height dimensions of 120” x 120”, was tested in accordance with the following Standards at Intertek:  UL10B, UL10C, UL10D and NFPA 252
Test Method Property Results
UL10D Fire Tests For Fire Protective Curtains 120 Minutes
UL10B, UL10C, and NFPA 252 Fire Tests For Fire Protective Curtains without hose stream 20 Minutes
 NOTE:  Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.
 
SIZE LIMITATIONS
The following size limitation table pertains to the fire-resistance rated Smoke Guard Model M2500 system with SGTex-30 fabric curtain only. 
Certification Procedure Maximum Area Maximum Width Maximum Height
LABEL (Tested) 100 sq ft 10'-0" 10'-0"
CERTIFICATE/LABEL  unlimited* unlimited* unlimited*
*The AHJ may approve oversize doors with no size limitation based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size.
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationFebruary 13, 2020
Certificate NumberWHI20 - 20797314
CriteriaNational Building Code of Canada or applicable Provincial Building Code
CriteriaASTM E84 (2013a)
CriteriaUL 1784 (2015)
CriteriaUL 10(d) (2014)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 30 00 Specialty Doors and Frames
CSI Code08 34 00 Special Function Doors
Listing SectionCATEGORY I - SMOKE & DRAFT CONTROL DOOR ASSEMBLIES
Spec ID32807