Steel-Faced (14, 16, 18 & 20 gauge) (707) (Polystyrene or Honeycomb Core Type) (Flush, Simulated Panel Type), Swinging Door for installation in 3 hour locations. For use in listed (3-sided) 16 gauge welded or KD steel frames meeting UL-63 or as per frame manufacturer's listing(s).
Limitations*:
Mortise or Cylindrical Latches with maximum 5” backset/Mortise Type Exit Devices/Surface-Mounted Vertical Rod fire exit devices/Rim-Type fire exit devices/Concealed Vertical Rod exit devices/Deadbolts/Extension Bolts with a maximum extension of 24”/Surface Bolts/Surface-Mounted Closers/Surface-mounted Protection plates/Louver/Vision Light Kit - Maximum 1296 in2 - 20/45 minutes; 100 in2 - 60/90 minutes/Surface-Mounted Door Bottoms/Astragal Optional on Pairs/Temperature Rise - Greater than 650°F at 30 minutes.
| Sizes: With 14 Gauge Faces: |
| Configuration |
Maximum Size (Honeycomb) |
Maximum Size (EPS) |
| Single |
4’-0” Wide x 9’-0” High (up to 3 hour) |
4’-0” Wide x 8’-0” High (up to 3 hour) |
| Standard Pair with Fixed Mullion |
8'-0" Wide x 9'-0" High (up to 3 Hour)
[4'-0" Wide x 9'-0" High Leaf Size] |
8'-0" Wide x 8'-0" High (up to 3 hour)
[4'-0" Wide x 8'-0" High Leaf Size] |
| Sizes with 16 & 18 Gauge Faces: |
| Configuration |
Maximum Size (Honeycomb) |
Maximum Size (EPS) |
| Single |
4’-0” Wide x 8’-0” High (up to 3 hour)
4’-3” Wide x 9’-0” High (up to 1-1/2 hour) |
4’-0” Wide x 8’-0” High (up to 3 hour) |
| Pairs |
8’-0” Wide x 8’-0” High (up to 3 hour)
8’-6” Wide x 9’-0” High (up to 1-1/2 hour) |
8’-0” Wide x 8’-0” High (up to 3 hour)
|
| Double Egress |
8’-0” Wide x 8’-0” High (up to 3 hour)
8’-6” Wide x 9’-0” High (up to 1-1/2 hour) |
8’-0” Wide x 8’-0” High (up to 3 hour)
|
| Sizes: With 20 Gauge Faces: |
| Configuration |
Maximum Size (Honeycomb) |
Maximum Size (EPS) |
| Single |
4’-0” Wide x 8’-0” High (up to 3 hour)
4’-3” Wide x 9’-0” High (up to 1-1/2 hour) |
4’-0” Wide x 8’-0” High (up to 3 hour) |
| Pairs |
8’-0” Wide x 8’-0” High (up to 3 hour)
8’-6” Wide x 9’-0” High (up to 1-1/2 hour) |
8’-0” Wide x 8’-0” High (up to 3 hour) |
| Double Egress |
8’-0” Wide x 8’-0” High (up to 3 hour)
8’-6” Wide x 9’-0” High (up to 1-1/2 hour) |
8'-0" Wide x 7'-2" High (up to 3 hour)
8’-0” Wide x 8’-0” High (up to 1-1/2 hour) |
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.
Testing Standards: UL 10C, NFPA 252, & CAN/ULC S104 (Positive Pressure)
| Wired Glass |
| Rating |
Max. Visible Area |
Comments |
| 60/90 minute |
100 in2 |
Channel Not required; Pemko FG3000 and Pilkington/Asahi Glass |
| 60/90 minute |
552 in2 Single
1872 in2 Multiple |
Channel Required; Pemko FG3000 and Pilkington/Asahi Glass |
| 20/45 minute |
2856 in2 Single/Multiple |
Channel Required; Pemko FG3000 and Pilkington/Asahi Glass |
| 20/45 minute |
1296 in2 |
Channel Not required; Closed Cell Glazing Material and Pilkington/Asahi Glass |
| 20 minute without hose (UL 10C and NFPA 252 Only. This variation is not approved for CAN/ULC S104) |
2994 |
Channel Required; Closed Cell Glazing Material and Pilkington/Asahi Glass |
| FireLite® Glazing |
| Rating |
Max. Visible Area |
Comments |
| 3 hour |
100 in2 |
Channel Not Required |
| 60/90 minute |
1,296 in2 |
Channel Not Required |
| 90 minute Temp rise |
100 in2 |
Temp Rise Door (uses Mineral core material) |
| 45/60 minute |
1296 in2 |
|
| 20 minute without hose (UL 10C and NFPA 252 Only. This variation is not approved for CAN/ULC S104) |
2835 in2 |
Without Hose |
Evaluated to the following...
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UL 10C"