Steel-Faced (16, 18 gauge) (607) (Polystyrene Core Type) Swinging Door for installation in and up to 3 hour locations. For use in listed (3-sided) 16 gauge welded or KD steel frames meeting UL-63 or as per frame manufacturer's listing(s).
Limitations*: Mortise or Cylindrical Latches with maximum 5" backset / Surface-Mounted Vertical Rod fire exit devices / Rim-Type fire exit devices / Concealed Vertical Rod exit devices / Deadbolts / Flush Bolts / Closers / Louver / Vision Light Kit - see chart below / "Z" Astragal.
| Configuration |
Maximum Size* |
| Single Swing |
4'0" wide x 8'0" high |
| Standard Pairs |
8'0" wide x 8'0" high |
| Double Egress Pairs |
6'0" wide x 8'0" high; allowed up to 3 hour max; vertical exit rods required on both doors. |
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.
VISION PANELS FOR ALL DOORS
Wired Glass:
| Rating |
Max. Visible Area |
Comments |
| 60/90 minute |
100 sq.in. |
Channel Not required; Pemko FG3000 and Pilkington/Asahi Glass |
| 60/90 minute |
552 sq.in. Single
1872 sq.in. Multiple |
Channel Required; Pemko FG3000 and Pilkington/Asahi Glass |
| 20/45 minute |
2856 sq.in. Single/Multiple |
Channel Required; Pemko FG3000 and Pilkington/Asahi Glass |
| 20/45 minute |
1296 sq.in. |
Channel Not required; Closed Cell Glazing Material and Pilkington/Asahi Glass |
20 minute without hose
(UL 10C and NFPA 252 Only. This variation is not approved for CAN/ULC S104) |
2994 sq.in. |
Channel Required; Closed Cell Glazing Material and Pilkington/Asahi Glass |
FireLite® Glazing:
| Rating |
Max. Visible Area |
Comments |
| 3 hour |
100 sq.in. |
Channel Not Required |
| 60/90 minute |
1296 sq.in. |
Channel Not Required |
| 90 minute Temp rise. (requires mineral core) |
100 sq.in. |
Temp Rise Door |
| 45/60 minute |
1296 sq.in. |
|
20 minute without hose
(UL 10C and NFPA 252 Only. This variation is not approved for CAN/ULC S104) |
2835 sq.in. |
Without Hose |
Evaluated to the following...
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UL 10C - NFPA 252 - CAN/ULC S104".