Product Covered:
Smoke Guard Model M4000 curtain assembly.
Product Description:
The Smoke Guard M4000 systems consist of fire and smoke resistance rated filament glass fabric (SGTex-30 or SGTex-32) that is folded into a sheet metal housing. Contained in a sheet metal housing, the curtain assembly is comprised of drive means and associated electronics. The curtain edges are captured in optional vertical side guides (depending on the shape of the system). During system deployment, the bottom edge of the curtain is attached to a weighted bottom pan. Aluminum finish covers may be attached to the weighted bottom pan using pressure-sensitive adhesive with or without the use of rivets.
If the system encounters an alarm, the releasing device activates deploying the curtain. In the event of main power failure, an integrated battery system maintains the system in ready position. Should main and backup power systems fail, the curtain will deploy in a controlled manner under the influence of gravity (Gravity Fail Safe). If required, wall switches are provided on each side of the curtain, allowing occupants to momentarily raise the curtain to egress. After the alarm condition clears, the curtain automatically rewinds into the housing.
AIR LEAKAGE RATINGS
The following ratings pertain to the Smoke Guard Model 4000 system using SGTex-30 curtain fabric.
Test Standard |
Test Type |
Ratinga |
UL 1784 |
Ambient & Elevated Temperatures |
≤ 3.0 cfm/ft2 at 0.10 in. of w.c. |
aThis assembly was evaluated
without an artificial bottom seal. The assembly
may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019).
FLAME SPREAD RATINGS
The following ratings pertain to the Smoke Guard Model 4000 system with the fabrics as noted.
Test Standard |
Flame Spread |
Smoke Development |
ASTM E84 (SGTex-30 and -32) |
<25 |
<450 |
CAN/ULC S102 (SGTex-30) |
0 |
20 |
FIRE RATINGS
The following ratings pertain to the Smoke Guard Model 4000 system with SGTex-30 or SGTex-32 curtain fabrics.
Test Standard |
Rating |
UL 10D |
120 minute |
UL 10B, UL 10C, NFPA 252 |
20 minute without hose stream |
The UL 10B, UL 10C, and NFPA 252 standards apply only to 20 minute fire endurance ratings without hose stream. Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product is ultimately at the discretion of the Authority Having Jurisdiction.
MINIMUM SIZE LIMITATIONS (SMOKE-RATED ASSEMBLIES)
System Type |
Minimum Curtain Height |
Minimum Total Plan Length* |
Closed (Without Side Guides) |
8'-0" |
16'-0" |
Open (With Side Guides) |
8'-0" |
23'-0" |
*Total Plan Length is the sum of the width of all curtain panels.
MAXIMUM SIZE LIMITATIONS (FIRE-RATED ASSEMBLIES)
Certification Procedure |
Maximum Areaa |
Maximum Dimensionsa |
LABEL (Tested) - Individual Panel |
100 sq ft |
10'-0" Wide x 10'-0" High |
LABEL (Tested) - Complete Assembly |
131 sq ft |
13'-2" Total Plan Lengthb x 10'-0" High |
CERTIFICATE/LABEL |
unlimitedc |
unlimitedc |
aThe size limitation is based on a three-sided assembly tested with two 19" wide by 10' high sides and a front face 10' wide by 10' high.
bTotal Plan Length is the sum of the width of all curtain panels.
cThe AHJ may approve oversize doors with no size limitation based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size.