Product Covered:
Smoke Guard Model M3000 horizontal curtain assembly.
Product Description:
The Smoke Guard M3000 horizontal systems consist of smoke resistance rated filament glass fabric (SGTex-30 or SGTex-32) wound onto a tube containing an internal drive system. Contained in a sheet metal housing, the curtain assembly is comprised of support rollers and associated electronics. The curtain edges are captured in side guides during system deployment and the leading edge of the curtain is attached to a leading edge bar. If the system encounters an alarm, the releasing device activates deploying the curtain. In the event of main power failure, an integrated battery system maintains the system. Should the main power systems fail, the curtain will deploy in a controlled manner using a battery backup system. After the alarm condition clears, the curtain automatically rewinds into the housing.
FLAME SPREAD RATINGS
Test Standard |
Flame Spread |
Smoke Development |
ASTM E84 (SGTex-30 or -32) |
≤ 25 |
≤ 450 |
CAN/ULC S102 (SGTex-30) |
0 |
20 |
FIRE-RESISTANCE RATINGS (With SGTex-30 or SGTex-32)
Test Standard |
Test Type |
Ratinga |
UL 10D |
Fire Endurance |
120 minutes |
UL 10B, UL 10C, and NFPA 252 |
Fire Endurance |
20 minutes without hose stream |
aThe UL 10B, UL 10C, and NFPA 252 standards apply to 20 Minute Fire Endurance ratings without hose stream only. Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.
SIZE LIMITATIONS
Certification Procedure |
Maximum Area |
Maximum Width |
Maximum Height |
LABEL (Tested) |
178.75 sq ft |
10'-10" |
16'-6" |
CERTIFICATE/LABEL |
unlimited* |
unlimited* |
unlimited* |
*The AHJ may approve oversize doors with no size limitation based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size.