FIRE RESISTANT PRODUCTS & COMPONENTS
CATEGORY A DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Category "A" Wood Composite Core, swinging door for use in 20 through 90 minute positive pressure assemblies (also eligible for use in neutral pressure assemblies).
CATEGORY B DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Category "B" Wood Composite Core, swinging door for use in 20 through 90 minute positive pressure assemblies (also eligible for use in neutral pressure assemblies). A surface applied Category G intumescent edge seal system is required
.
PRODUCT COVERED
Creative Composites 20-90 Minute Wood Composite Fire Door
PRODUCT DESCRIPTION
Hardware Limitations: Cylindrical / Cylindrical with Deadbolt / Mortise / Card Reader / Butt Hinges / Spring Hinges / Continuous Hinges / Concealed Hinges / Pivots / Surface-Mounted Vertical Rod Fire Exit Devices / Rim-Type Surface Mounted Fire Exit Devices / Surface Bolts or Mortised Flush Bolts / Surface Mounted or Concealed Door Bottoms / Surface Mounted or Concealed Closers or Overhead Stops / Viewer / Vision Kit: Temperature Rise = Maximum of 960 in
2 in temperature rise glazing for a 45-90 minute rating; Non-Temperature Rise = 2,176 in
2 for a 45 minute rating and 1,344 in
2 for a 60-90 minute rating / Raceway / EPT / Plant-Ons / Protection Plates / Reveals and Inlays.
The doors noted within this listing may be installed with a 3/16” (maximum) gap between the door and frame interface (not allowed at the meeting edges of pairs) for a 60 minute rating (at the discretion of the AHJ) for use in any listed “Category C – Standard Frame” (grouted or un-grouted) only. A listed fire rated strike shim is required to maintain full engagement of the latch bolt into the strike of the frame when using a listed passage door lock with a 1/2” throw or otherwise a listed passage door lock with a 3/4” latch bolt throw is required. Maximum 4'0" wide x 8'0" high singles and maximum 8'0" wide x 8'0" high standard pairs and double egress.
Configuration Maximum Size
Single 4'0" wide x 9'0" high
Standard Pair See Table below.
Double Egress See Table below.
* See table and comments below.
Duration (minutes) |
Maximum size
(w x h) |
Swing |
Latching |
Metal Edge
(5") |
Comments |
90 |
8'0" by 9'0" |
Std Pair |
SVR/LBR
2 Pt. |
No |
Requires thermal pin door to door & MD Core |
90 |
8'0" by 8'0" |
Std Pair |
SVR
4 Pt. |
No |
None |
90 |
8'0" by 8'0" |
Std Pair |
3 Pt. latching Auto or manual flushbolts |
No |
Cylindrical or Mortise minimum 1/2" throw |
90 |
8'0" by 9'0" |
Std Pair |
3 Pt. latching Auto or manual flushbolts |
No |
Cylindrical or Mortise minimum 1/2" throw |
90 |
8'0" by 8'0 |
Double Egress |
SVR/LBR |
No |
Requires 2 thermal pin door to door & HD Core |
90 |
8'0" by 8'0" |
Double Egress |
SVR
4 pt. |
No |
Must have top and bottom rod Hardware |
90 |
8'0" by 8'0 |
Double Egress |
CVR/CVC
2 pt. |
Yes |
Requires thermal pin door to door |
90 |
8'0" by 7'0" |
Double Egress |
CVR
2 pt. |
Yes |
None |
90 |
6'0" by 9'0" |
Std. Pair |
CVR 4 pt. |
Yes |
Bottom latches required. |
90 |
8'0" by 7'0" |
Std. Pair |
CVR 2 pt. |
Yes |
No |
90 |
8'0" by 7'0" |
Std. Pair |
SVR/LBR 2 pt. |
No |
Thermal pins not required |
60 |
8'0" by 8'0" |
Double Egress |
SVR/LBR |
No |
Requires thermal pin door to door & MD Core |
60 |
8'0" by 7'0" |
Double Egress |
SVR/LBR |
No |
Thermal pins not required |
60 |
8'0" by 9'0" |
Std. Pair |
SVR
2 pt. |
No |
Requires thermal pin door to door & MD Core |
60 |
8'0" by 8'0" |
Std. Pair |
SVR
2 pt. |
No |
Requires thermal pin door to door |
60 |
6'0" by 9'0" |
Std. Pair |
SVR 2pt. |
No |
Requires thermal pin door to door |
60 |
6'0" by 9'0" |
Std. Pair |
CVR 2pt. |
Yes |
Requires thermal pin door to door |
60 |
8'0" by 8'0" |
Std |
SVR/2pt |
No |
Requires thermal pin door to door |
45 |
8'0" by 9'0" |
Double Egress |
CVR/SVR/LBR |
No |
Requires 2 thermal pin door to door & LD Core |
45 |
8'0" by 9'0 |
Std.
Pair |
CVR/CVC/LBR
|
Yes |
Requires thermal pin door to door |
The product noted above has been tested and qualified per UL 10C, NFPA 252, and CAN/ULC S104 for a 90 Minute Positive Pressure Fire Rating.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing.
The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.