Intertek Directory of Building Products

Sioux Chief Manufacturing - PowerPEX and PowerPEX Barrier Pipes Company: Sioux Chief Manufacturing Company, Inc.

DESCRIPTION

Sioux Chief PowerPEX and PowerPEX Barrier Pipes are manufactured from a crosslinked high density polyethylene (HDPE) for use in hot and cold water distribution systems. 


FLAME SPREAD RATINGS
 
ASTM E84 - Surface Burning Characteristics
Product Size Flame Spread
 Classification
Smoke Developed Classification
PowerPEX* 1/4 to 2 in. <25 <50
PowerPEX Barrier* 1/2 to 1 in. <25 <50
 
CAN/ULC-S102.2 - Surface Burning Characteristics
Product Size Flame Spread
 Classification
Smoke Developed Classification
PowerPEX* 1/4 to 2 in. <25 <50
PowerPEX Barrier* 1/2 to 1 in. <25 <50

*Ratings apply when tubing is field insulated with fiberglass insulation conforming to the following:
  • ASTM E84 Listed
  • Flame Spread Index of <25
  • Smoke Developed Index of <50
  • Wall thickness – minimum 1/2”
FIRE RATINGS
 
Test Stadnard Rating Design Number
CAN/ULC-S101, ASTM E119 2 Hour SCMC/DWP 120-01
CAN/ULC-S101, ASTM E119 1 Hour SCMC/DWP 60-01
CAN/ULC-S101, ASTM E119 1 Hour SCMC/DWP 60-02
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S101 (2007)
CriteriaASTM E119 (2010)
CriteriaCAN / ULC S102.2 (2010)
CriteriaASTM E84 (2012)
CSI Code22 11 00 Facility Water Distribution
Listing SectionBUILDING MATERIALS WITH SURFACE BURNING CHARACTERISTICS
Spec ID36150
Design Documents
Public Documents
No Results