PRODUCT COVERED
SECURALL 3 Hour Fire Rated FEMA 320/361 Door
SECURALL 3 Hour Fire Rated FEMA 320/361 Door and Frame Assembly
PRODUCT DESCRIPTION
Fire Rated Door and Fire Rated Door/Frame Assembly. Door construction consists of 12 GA Galannealed, Galvanized Steel or Cold Rolled Steel door panel with steel stiffeners and mineral wool or fiberglass insulation. Door frame consists of 12 GA Galvannealed, Galvanized, or Colled Rolled steel.
MAXIMUM SIZES
Single Swing Door
42" wide x 84" high Nominal
Single Swing Frame
42" wide x 84" high Nominal
Pairs
Not allowed
Pairs - Frame
Not allowed
RATINGS
Up to 3 hour positive pressure to the following standards:
UL 10C (2015)
CAN/ULC S104 (2015)
LIMITATIONS
Install Fire Door in minimum 12 GA Steel, Fire Rated Frame approved to UL Subject 63, UL 10C, NFPA 252 (positive pressure), or CAN/ULC-S104, and compliant with applicable NFPA 80 requirements
When istalled in fire rated gypsum/steel stud or gypsum/wood stud construction, the following conditions apply:
-
Anchoring options shall comply with UL Subject 63 and NFPA 80
-
Minimum 2x6 wood studs
-
Minimum 16 GA steel studs
-
Minimum number of 5/8-in. Type X gypsum board per side:
-
1h - 1 layer
-
2h - 2 layers
-
3h - 3 layers
The door and frame assembly shall be de-rated to matchthe fire rating of the wall if installed in less than 3h rated construction.
Use minimum Grade 1 Fire Rated Latch with minimum 3/4-in. latch throw.
This door shall be installed in accordance with NFPA 80 requirements.
This Listing is for fire resistance only and does not apply to FEMA requirements which are outside of the scope of this listing.