McKEON SmokeFighter® Model D150 and D150E Curtain Assemblies are for use as smoke barrier curtain assemblies. All assemblies may be configured with or without an overlap, and Model D150E assemblies contain a passage door sealed with a hook & loop fastener. Assemblies may include a non-porous vision panel. See details below for limitations on overlaps, passage doors, and vision panels.
AIR LEAKAGE RATINGS
| Test Standard |
Test Type |
Ratinga |
| UL 1784 |
Ambient Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
| UL 1784 |
Elevated Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
aThis assembly was evaluated without the use of an artificial bottom seal and may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC.
CODE COMPLIANCE RESEARCH REPORT
| Evaluation Method |
Building Code |
CCRR Number |
| UL 1784 |
2024, 2021, 2018 IBC
2024, 2021, 2018 IFC
2023, 2020 FBC
2022 CBC
2023 LABC
2024, 2021, 2018 NFPA 101 |
CCRR-0455 |
SIZE LIMITATIONS
| Minimum (Tested) Sizea |
Maximum Sizeb |
| 78” tall x 29.5” wide |
48’0” tall x 500’0” wide |
aClear opening dimensions (i.e., tip-to-tip width between side guides and drop height below headbox)
bOversize labels are not required for this assembly. Assembly dimensions must comply with the minimum and maximum values listed above.
Minimum Overlap: 15-3/4"
Maximum Hook & Loop length: 8' 0"
Clear plastic (non-porous) vision panels must be sandwiched into fabric curtain and double stitched. Outer stitch must be at least 1" from visible panel and at least 3/4" from inner stitch. Inner stitch must be at least 1/4" from visible panel. At least 1.5" of curtain material must overlap vision panel. No size or quantity limits apply to vision panels when installed as described.