Smoke Guard® Model 2500E
Company: Smoke Guard, Inc.
Product Covered:
Smoke Guard Model 2500E fire and smoke curtain assembly
Product Description:
The Smoke Guard M2500E system consists of a filament glass fabric curtain (constructed of SGTex-30 fabric) wound onto a tube containing an internal drive system. The curtain incorporates one or more overlapping egress passages constructed of SGTex-32 fabric (see below for further details). Contained in a sheet metal housing, the curtain assembly is comprised of support rollers and associated electronics. Sewn loops along the curtain edges are captured in vertical side guides during system deployment and the bottom edge of the curtain is attached to a weighted bottom bar. If the system encounters an alarm, the releasing device activates deploying the curtain. In the event of main power failure, an integrated battery system maintains the system. Should main and backup power systems fail, the curtain will deploy in a controlled manner under the influence of gravity (Gravity Fail Safe). If required, wall switches are provided on each side of the curtain, allowing occupants to momentarily raise the curtain to egress. After the alarm condition clears, the curtain automatically rewinds into the housing.
The Smoke Guard M2500E system is recognized for use as a fire and smoke control system in fire-resistance rated construction, as described in the tables below.
To maintain compliance with the listed fire ratings and an air leakage ≤3.0 cfm/ft2 at up to 0.10 in. of w.c. at ambient and elevated temperatures, the minimum curtain area that may contain two overlapping egress passages is 250 ft2. The minimum curtain area that may contain three overlapping egress passages is 350 ft2. A minimum of 4 lineal feet of curtain must remain between egress doors. Overlapping egress passages in curtains that are less than or equal to 102 inches in height shall be a maximum of 80 inches in height.
The Smoke Guard M2500E system must be installed in accordance with the manufacturer’s instructions.
FLAME SPREAD RATINGS
Test Standard |
Flame Spread |
Smoke Development |
ASTM E84 |
≤ 25 |
≤ 450 |
AIR LEAKAGE RATINGS
Test Standard |
Test Type |
Ratinga, b |
UL 1784 |
Ambient Temperature |
≤3.0 cfm/ft2 at up to 0.20 in. of w.c. |
UL 1784 |
Elevated Temperature |
≤3.0 cfm/ft2 at up to 0.30 in. of w.c. |
aThis assembly was evaluated with an artificial bottom seal. The assembly is not to be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) or for hoistway opening protection and lobby doorways where prohibited in Chapter 30 of the 2018 IBC.
bWhen installed in a minimum size of 10 ft x 10 ft containing a single overlapping egress passage.
FIRE RATINGS
Test Standard |
Test Type |
Ratinga, b |
UL 10D |
Fire Endurance |
120 Minutes |
UL 10B, UL 10C, and NFPA 252 |
Fire Endurance |
20 minutes without hose stream |
aThe UL 10B, UL 10C, and NFPA 252 standards apply to 20 Minute Fire Endurance ratings without hose stream only. Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.
bCurtains exceeding the tested dimensions of 10 ft x 10 ft must have an oversize label, issued by Intertek, stating the door is constructed in accordance with the certified design except for size. Acceptance of the oversize door is at the discretion of the Authority Having Jurisdiction