Limitations: Cylindrical Latches, Deadbolt, Vision Lights - 100 sq.in., Viewers.
Door Sizes:
Single Swing:
-
Maximum Overall Width: 4' 0"
-
Maximum Overall Height: 8' 0"
-
Thickness: 1-3/4"
-
Maximum Inner Door Width: 2'6"
-
Maximum Inner Door Height: 5'6"
-
Thickness: 1-3/4"
Standard Pair and Double Egress: Not Allowed.
RATINGS
20 Minute Positive Pressure with Hose Stream
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL 10 (c) Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)