Intertek Directory of Building Products

JELD-WEN Aurora 20 Minute Composite Fire Door and AuraLast Frame Assembly Company: JELD-WEN, Inc.

Aurora 20 minute composite fire door for installation in 20-minute locations (with hose stream).  Category B fire door - additional edge-sealing system is required.

 

Maximum Sizes:

 

 

Single Swing 36 in. wide x 96 in. high
Pairs Not permitted

Limitations:   Mortise latches, Cylindrical latches with minimum 1/2 in. bolt throw and up to 2-3/4  in. backset, cylindrical deadbolts, surface applied hardware, viewers, surface mount bolts.  Arch-top permitted within dimensions noted above.

Jeld-Wen AuraLast Treated 20 Minute Single Swing Wood Door Frame (Pine) (Knock-Down) for installation in 20 minute locations in steel/wood stud drywall or masonry openings.

Maximum Opening Size 3'0" wide x 8'0" high
Maximum Overall Dimensions 3' 1-11/16" wide x 8' 1-1/4" high
Minimum Wall Thickness 4-1/2"

LIMITATIONS
Any Category G gasket listed for use with wood edge doors. Category G gasket must be installed on kerfed and non-kerfed frames in positive pressure applications. Steel/wood stud drywall or masonry openings.

EVALUATED TO THE FOLLOWING

This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.

 

All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.

 

All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C".

Listing Report Return to Search
Attributes
CriteriaUBC 7-2 (1997)
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min PP Category D Door/Frame Assemblies
Listing SectionCATEGORY D - DOOR/FRAME ASSEMBLIES
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID39369
SwingSingle Swing
Design Documents
No Results
Public Documents
No Results