20-minute without hose Steel-Skin Foam-Filled Fire Door.
Field-Applied
gasket is required (
Category H gasket on the header and sides of the frame, Pemko S88, Schlegel kerf gasket or equivalent).
Limitations: Cylindrical locks and latches, deadbolts, surface mount hardware, viewers,
protection plates to 16" high.
Configuration |
Maximum Size* |
Single |
3' 0" wide x 6' 8" high |
*See manufacturer's installation instructions for additional information, restrictions and limitations.
Jeld-Wen AuraLast Treated 20 Minute Single Swing Wood Door Frame (Pine) (Knock-Down) for installation in 20 minute locations in steel/wood stud drywall or masonry openings.
Maximum Opening Size |
3'0" wide x 6'8" high |
Maximum Overall Dimensions |
3' 1-11/16" wide x 6' 9-1/4" high |
Minimum Wall Thickness |
4-1/2" |
LIMITATIONS
Steel/wood stud drywall or masonry openings.