Intertek Directory of Building Products

CENTRIA - TotalClad, TotalClad ISS, and TotalClad Xrib (Roof) Insulated Metal Panels Company: Centria, A Nucor Company

CENTRIA TotalClad, and TotalClad ISS & Total Clad Xrib (Roof) Insulated Metal Panels

TotalClad, TotalClad ISS, and TotalClad Xrib Panels are composite panels made of a polyurethane foam core which is foamed in place between the roll formed steel faces. 

TotalClad and TotalClad ISS min. panel thickness is 2 in.  TotalClad Xrib min. panel thickness is 1-1/2 in.  Max. panel thickness is 6 in. for all panels.  Panel width may be 12 in. to 44.5 in.  Panel face thickness may be 26 GA to 22 GA.  Panel face profile may be any of the published standard profiles.  TotalClad Panels may be installed in the vertical or horizontal orientation.  TotalClad ISS panels are installed as roof panels.

One edge of the panel is formed with a unique "male" connection profile, while the other edge is formed with the corresponding “female” connection profile.  The ends of the panel are cut straight and square.  Panels are not fully encapsulated by the metal skin—the foam core is exposed around all edges.  The panels are installed through interlocking of adjacent panels, and flashing installed over the panel ends providing a continous steel skin weather barrier and non combustible steel face protecting the polyurethane core.  The panel core is a two-component (Part A and Part B) polyurethane foam that is mixed and injected between the steel skins. 

 RATINGS
 
PRODUCT STANDARD RATING
TotalClad, TotalClad ISS, and TotalClad Xrib Panel Assembly ASTM E84 (2010b) Flame Spread: <25
Smoke Developed: <450
TotalClad, TotalClad ISS, and TotalClad Xrib Foam Core ASTM E84 (2010b) Flame Spread: <25
Smoke Developed: <450
TotalClad, TotalClad ISS, and TotalClad Xrib Panel Assembly with 2 layers of 5/8-in., Type X Gypsum Sheathing ASTM E119 (2010e) 1 Hour Non Load Bearing Fire Rating
TotalClad, and TotalClad Xrib Panel Assembly CAN/ULC S101 (2007) Meets 15 Minute Stay in Place Requirements
(See Design No. MSN/CWP 15-01)
TotalClad, TotalClad ISS, and TotalClad Xrib Panel Assembly with 2 layers of 5/8-in., Type X Gypsum Sheathing CAN/ULC S101 (2007) 1 Hour Non Load Bearing Fire Rating
TotalClad, TotalClad ISS, and TotalClad Xrib Panel Assembly CAN/ULC S102 (2010) Flame Spread: 0
Smoke Developed: 17
Fuel Contribution Value: 0 (average)
TotalClad, TotalClad ISS, and TotalClad Xrib Foam Core CAN/ULC S102 (2010) Flame Spread: 10
Smoke Developed: 40
Fuel Contribution Value: 0 (average)
TotalClad ISS and TotalClad Xrib Panel Assembly CAN/ULC S126-M86 (R2000) Flame Spread: Pass
Smoke Developed: Pass
TotalClad &
TotalClad Xrib Panel Assembly
CAN/ULS S134 (1992) Flame Spread: < 5m
Heat Flux: <35 KW/m2
Meets NBC 2005 Section 3.1.5.5
(See Design No. MSN/CWP 30-02)
TotalClad Panel Assembly CAN/ULC S138 (2006) Meets Requirements
TotalClad, TotalClad ISS, and TotalClad Xrib Panel Assembly NFPA 259 (2008) 11150.8 Btu/lb Average
TotalClad & TotalClad Xrib Panel Assembly NFPA 285 (2006) Meets Requirements
(See Design No. MSN/CWP 30-01)
TotalClad, TotalClad ISS, and TotalClad Xrib Panel Assembly NFPA 286 (2006) Meets IBC 2009 Section 803.1.2.1
15 Minute Duration
TotalClad ISS & TotalClad Xrib Panel Assembly ASTM E 108 (2011)
and
CAN/ULC S 107 (2010)
Class A Spread of Flame – Pass†
Class A Intermittent Flame - Pass†
Class A Burning Brand - Pass†
(†Unlimited Roof Slope
 
Product Product Approval No.
TotalClad XRib Panels FL # 21858
TotalClad Panels - Multiple Models FL # 21859
 
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S107 (1987)
CriteriaCAN / ULC S101 (2007)
CriteriaCAN / ULC S126-M86 (R2000)
CriteriaCAN / ULC S134-92 (R1998)
CriteriaNFPA 286 (2006)
CriteriaNFPA 259 (2008)
CriteriaCAN / ULC S138 (2006)
CriteriaASTM E108 (2010a)
CriteriaCAN / ULC S102 (2010)
CriteriaASTM E84 (2012)
CriteriaNFPA 285 (2012)
CriteriaASTM E119 (2012a)
CSI Code07 40 00 Roofing and Siding Panels
CSI Code07 42 43 Composite Wall Panels
Listing SectionBUILDING PANELS
Spec ID39621